UMSITRPDS3-1
On-Line Operation
November 2010
6-3
6.1.3 Unit/Bargraph Display
This alphanumeric display has five 14-segment fields in the lower right quadrant of the display; see
below. It shows the selected engineering unit as a percentage, engineering unit, or current value. If
desired, a bargraph which represents the percentage pressure value in the range from 0-100% can
alternate with the engineering unit. The bargraph function is turned off in the default setting.
Engineering Unit
Bargraph
The unit/bargraph display is also used to display a scrolling error, warning, or alarm message.
6.1.4 Error Message
The message “Error” will be displayed in the Numeric display should a
transmitter hardware or software problem occur. A message describing the
error will scroll horizontally through the unit/bargraph display. This
information is also available at the HART Communicator.
6.1.5 Output Signal Range
The output signal is divided into defined areas.
The transmitter converts the measured pressure into an output current that is
normally in the range of 4-20 mA.
Measured values below and above the range limits are also displayed. The UNDER message or OVER
message for the selected unit appears alternately in place of the engineering unit or bargraph. The
overflow range, shown in the following figure, can be set using the HART Communicator. When an
upper or lower range limit is exceeded, the output current remains linear and a status arrow appears on the
transmitter display; see Table 6-1.
Summary of Contents for 7MF4033 series
Page 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Page 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Page 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Page 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Page 197: ......
Page 198: ......
Page 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Page 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Page 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Page 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...