Table B-5
Formats of the substatus bits
Bit
5
Bit
4
Bit
3
Bit
2
Profile Designation
Meaning
0
0
0
1
configuration error
Parameter error, i.e. upper and lower value for meas‐
uring or output scale identical
0
0
1
1
device failure
RAM or EEPROM defective;
Diagnostic bit "Memory error" is also set and the diag‐
nosis message "RAM error" or "EEPROM error" dis‐
played locally
sensor failure
Measurement was not possible;
Diagnostic bit "Memory error" is also set and the diag‐
nosis message "Measuring path fault" displayed locally
0
1
1
1
out of service
Corresponding function block is in "Out of service"
mode (see parameter "MODE_BLK actual")
0
0
0
0
non specific
Measurement contains too many implausible meas‐
ured values, e.g. due to solids or gas bubbles in the
medium.
Diagnostic bit "Memory error" is also set and the diag‐
nosis message "RAM error" or "EEPROM error" dis‐
played locally
0
0
0
1
last usable value
Failsafe mode: the current measured value has been
replaced with the last good measured value
0
0
1
0
substitute set
Failsafe mode: the current measured value has been
replaced with the agreed failsafe value
0
1
0
0
initial value
Failsafe mode or state before the first measurement:
the current measured value has been replaced with
the start value
0
1
0
0
sensor conversion not accurate
Measured value is outside the sensor limits
(Table 5-1, Page 30)
O.K.
Measured value is OK (normal state)
0
0
0
1
update event
A parameter with the "static" memory attribute has
been changed locally or on the PROFIBUS
0
0
1
0
active advisory alarm
Upper warning limit value has been exceeded or the
lower warning limit value has been undershot below
0
0
1
1
active critical alarm
Upper alarm limit value has been exceeded or the low‐
er alarm limit value has been undershot
Table B-6
Formats of the limit bits
Bit
1
Bit
0
Profile Designation
Meaning
0
0
O.K.
The measured value is within the limit values (normal state)
0
1
low limited
The measured value has exceeded the upper limit (alarm, warning or
sensor limit)
1
0
high limited
The measured value has exceeded the upper limit value (alarm, warning
or sensor limit)
1
1
constant
Measured value remains constant
PROFIBUS communication
B.4 Status bytes
SITRANS FUS060 with PROFIBUS PA
92