encoder inputs
The LMS5xx PRO/Heavy Duty has two encoder inputs (IN3 and IN4) that can be
selected via software.
The encoder pulses can be used to influence the size of so-called dynamic fields, for
example for speed-dependent vehicle monitoring. A dynamic field changes its length
with the speed measured e.g. by encoders.
SOPAS:
Project tree
,
LMS…
,
Parameters
,
Network/Interfaces/IOs
,
Digital Inputs 3+4 / Encoder
(HTL)/Sync
.
When stationary (V = 0 m/s), the evaluation field has the size of the configured basic
field. The size increases continuously with increasing speed until the largest field exten‐
sion is reached at maximum speed.
Digital outputs
The LMS5xx Lite has three digital outputs, the LMS5xx PRO/Heavy Duty six.
The outputs can be used as digital outputs to ground or as volt-free outputs
the inputs and outputs", page 69
For the
... / Device Not Ready
setting, the sensor always signals
Device Not Ready
regardless
of whether the outputs are switched by the field evaluation application or by SOPAS ET
telegrams.
SOPAS:
Project tree
,
LMS…
,
Parameters
,
Network/Interfaces/IOS
,
Digital Outputs
.
If the field evaluation application is being used to switch an output, the LMS5xx may
signal evaluation field breaches or contour breaches. In SOPAS ET, you can configure
which evaluation case affects which output.
External digital outputs
Up to 8 additional digital outputs can be controlled via a CAN extension module (part
no. 6038825 or 6041328). To use the additional outputs, the extension module must
be activated.
SOPAS:
Project tree
,
LMS531
,
Parameters
,
Network/Interfaces/IOS, External Digital Outputs
NOTE
For monitoring the extension module (heartbeat), module ID < 63 must be set.
Relay outputs
The LMS531 Lite has two relay inputs, the LMS531 PRO four. These can optionally
be configured to switch to HIGH or LOW when an object or person is detected in the
evaluation field.
Project tree
,
LMS531
,
Parameters
,
Network/Interfaces/IOS
,
Relay Outputs
.
There are the following options for configuration:
Table 15: LMS531 Lite/PRO: Status of outputs with object detection
Output
Configured HIGH logic
Configured LOW logic
Alarm output
Relay closed
Relay open
Error output
Relay closed
Relay open
Synchronization output
V
s
sensor is on
GND is on
Alarm output R (PRO: Pin 4 and Pin 6, Lite: Pin 3 and Pin 4) cannot be configured
because it serves as reference output. PRO: Pin 4 and Pin 6 or Lite: Pin 3 and Pin 4 are
internally connected (0 Ω),
see "Wiring the inputs and outputs", page 69
PRODUCT DESCRIPTION
3
8013796/1ALS/2021-03 | SICK
O P E R A T I N G I N S T R U C T I O N S | LMS5xx
43