13.7.3
Connecting supply voltage for the device in CDM420-0001
Device = Lector621 ECO = V2D621x-xxxxxYx (serial variant, Y = D or E)
Device
3
CDM420-0001
V
S
1
5
5
Shield
1
+24 V
2
GND
+24 V*
GND
S1
F
Shield
GND
.
.
.
.
.
.
ON
OFF
S1 : POWER
+24 V*
POWER
V
S
GND
V
S
-
+24 V
-
F
S 1
-
+24 V*
4
V
s
1
1
10
15
6
11
5
Cable
2
Figure 75: Connecting supply voltage for the device in CDM420-0001 connection module
1
Supply voltage V
S
2
Connecting cable permanently connected with the device (male connector, D-Sub-HD, 15-
pin)
3
Device
4
Connection module: female connector, D-Sub-HD, 15-pin
Function of switch S1
Table 67: Switch S1: Power
Switch setting
Function
ON
Supply v24 V connected to CDM420-0001 and device via fuse
and switch S1 as supply v24 V*.
Supply v24 V* can be additionally tapped at terminals 29 and
39.
OFF
CDM420-0001 and device disconnected from supply voltage.
Recommended setting for all connection work.
13.7.4
Wiring serial host interface RS-232 of the device in CDM420-0001
Device = Lector621 ECO = V2D621x-xxxxxYx (serial variant, Y = D or E)
ANNEX
13
8022502/15NT/2020-02-11 | SICK
O P E R A T I N G I N S T R U C T I O N S | Lector621
119
Subject to change without notice