CONFIGURABLE FUNCTIONS
4.13
Digital outputs
The Bulkscan has six digital outputs on which the sensor can signal that certain totals
have been reached, limits have been exceeded or dropped below, or the occurrence of
information/warnings.
The outputs can be used as digital outputs to ground or as floating outputs (see "6.3
Wiring the inputs and outputs to the external components“ on page 42).
Assignment
Switching condition
Behavior
Information/
Warnings
Information (
Yellow):
The sensor continues to
measure.
The output remains active until the prob-
lem is rectified.
Warnings (
Orange):
The sensor no longer
measures
Volume quota
Mass quota
Reaching the volume
quota or mass quota
The output behaves like a pulse output.
Volume flow rate
Mass flow rate
Center of gravity
Bulk density
Bulk height
Belt speed
• Dropping below the
lower limit
• Exceeding the upper
limit
The output behaves like a switching
output.
Tab. 3: Assignment and switching conditions for the digital outputs
Digital outputs
tab
Logic
You can configure the switching behavior on the occurrence of the switching condition:
• Active low: The digital output changes from HIGH to LOW (= active).
• Active high: The digital output changes from LOW to HIGH (= active).
Behavior as output Information/Warnings
Assignment
Description
All
All information/warnings are displayed
Invalid measuring points
Too many invalid measuring points within one scan
Bulk edge left
Bulk materials too close to the left end of the measurement field
Bulk edge right
Bulk materials too close to the right end of the measurement field
Conveyor edge left
Belt too far from the left end of the measurement field
Conveyor edge right
Belt too far from the right end of the measurement field
Contamination
Front screen contaminated
Tab. 4: Behavior as output Information/Warnings
It is possible to set a switching delay time. for the digital output.
Warnings that are present for a short time only are not issued via the digital output if
the switching delay times are long.
Behavior as pulse output
If the set
Volume quota
or Mass quota is reached, a pulse is transmitted from the digi-
tal output. You can set the
Pulse width
to between 20 ms and 10 s.