68
Technical Handbook
Parameter
Name
Default
P.0570
Mobile network mode
1-GSM/GPRS
P.0571
LTE category
2-CAT M and NB-Iot
P.0551
APN primary (access Point Name)
P.0552
APN primary username (optional)
P.0553
APN primary password (optional)
P.0554
APN primary (access Point Name)
P.0555
APN primary username (optional)
P.0556
APN primary password (optional)
P.0557
Connection mode
1-Stay connected
P.0558
Modbus/TCP enable
0-No
P.0559
Modbus/TCP port
502
•
P.0570
parameter configures the preferred Network Mode to:
➢
0 (“Automatic”):
automatic connection between GSM/GPRS/EDGE or LTE network.
In this mode, the device decides independently, based on the available networks and
signal strength, which type of network to connect.
When first power up, it will search with the following priority: CAT-M > NB-IOT >
GSM/GPRS/EDGE.
Search time depends on signal strength and active mobile networks detect.
I
t may
be necessary to wait several minutes before the first connection to the mobile
network is established.
➢
1 (“GSM/GPRS”):
connection to the GSM/GPRS/EDGE network only
➢
2 (“LTE”)
: connection to the LTE network only
•
P.0571
parameter configures the preferred LTE network mode to:
➢
0 (“CAT-M”):
connection to the CAT-M1 network only.
➢
1 (“NB-IoT”):
connection to the NB-IoT network only.
➢
2 (“CAT-M and NB-IoT”):
automatic connection between CAT-M or NB-IoT network
.
If you have a
SIM
not enabled for
LTE
connections (
CAT.M1 or NB-IoT
) or if these two new
technologies are not available, we recommend setting parameter
P.0570
to
1-GSM/GPRS
to
force the connection to the
GSM/GPRS/EDGE
network and make the first connection faster.
•
P.0551
parameter configures the APN (Access Point Name) of the mobile operator used.
Some operators require access credentials (username e password) to access the APN: in this
case use the parameters
P.0552
and
P.0553
to configure username and password. If access
credentials are not required (standard), leave
P.0552
and
P.0553
empty.
•
P.0557
parameter configures how the controller has to connect to the data mobile network:
➢
0
(“Disconnect every time
”). In this mode the controller connects to the data mobile
network every time it has to send data to “
Si.Mo.Ne
” server and disconnects as soon as
it has sent the data. If this mode is used, the data exchange with the Modbus/TCP protocol
with the controller is not possible.
➢
1
(“Stay connected
”). This mode is suggested: the controller connects to the data mobile
network as soon as possible and remains connected until it is possible. In this mode the
data exchange with the Modbus/TCP protocol with the controller is possible (BoardPrg3,
SicesSupervisor3).
•
P.0558
parameter activate/deactivate the data exchange with the protocol Modbus/TCP on
the mobile network: when it is enabled, the parameter
P.0559
configures the TCP port on
which the controller is able to communicate.
Page S.03 shows:
➢
the active connection type GSM, EDGE, LTE NB-IoT or
LTE CAT-M1.
➢
the Mobile Network Operator (MNO) currently
connected (Vodafone, TIM….). If the SIM card does not
return the full name the Mobile Country Code (MCC) +
Mobile Network Code (MNC) is shown.
➢
the mobile network signal intensity.
S.03 SERIAL COMMUN. |
LINK module: idle
Link type: SIM_7000G
Vodafone
LTE NB
85
|