230
Technical Handbook
Charge/discharge current
Adc
M.15
Average temperature
°C
M.15
Charge level
Ah
M.15
Bus voltage
Vdc
*
Central temperature
°C
*
Lateral temperature (1)
°C
*
Lateral temperature (2)
°C
*
Electronic card temperature
°C
*
Central heater command
%
*
Lateral heaters command
%
*
Date/time
s
*
Alarms/warnings
-
S.02
I/O status
-
-
LED lamps status
-
-
Model
-
M.16
Serial number
-
M.16
*: these data are not displayed; they are readable by HS315 via Modbus.
HS315 can use highlighted data instead of its measured ones.
The management of the alarm/warnings coming from the battery is like that of CANBUS
engines. In practice, HS315 handles only two cumulative:
•
W226: cumulative warnings of the batter
ies’ electronic cards.
•
W227: cumulative alarms of the
batteries’ electronic cards.
On page S.02, when one of the alarms/warnings is present, HS315 displays the active
diagnostic codes on the last line (rotating if more than one).
The possible codes are:
•
0: Minimum Ambient Temperature alarm"
•
1: Maximum ambient temperature warning
•
2: Maximum ambient temperature alarm
•
3: Minimum battery temperature alarm
•
4: Maximum battery temperature warning
•
5: Maximum battery temperature alarm
•
6: Minimum bus voltage warning
•
7: Minimum bus voltage alarm
•
8: Maximum bus voltage warning
•
9: Maximum bus voltage alarm
•
10: Maximum bus discharge current warning
•
11: Maximum bus discharge current alarm
•
12: Battery insulation warning
•
13: Main switch error alarm
•
14: Fuse blown alarm
Summary of Contents for HS 315
Page 1: ...File name EAAM058607EN docx Rev 07 Date 25 09 2019 ID Document EAAM0586 Product HS315...
Page 17: ...Technical Handbook xvii...
Page 18: ......
Page 23: ...Technical Handbook 5 Rear view Hall...
Page 254: ......