Technical Handbook 203
Type:
Warning
Related parameters:
P.9701
Battery temperature hysteresis.
P.9706
High battery temperature threshold.
P.9707
High battery temperature delay.
To disable:
P.9707 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery temperature remains
continuously above the threshold P.9706 for time P.9707.
Type:
Latched warning
Related parameters:
P.9701
Battery temperature hysteresis.
P.9708
Max battery temperature threshold.
P.9709
Max battery temperature delay.
To disable:
P.9709 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery temperature remains
continuously above the threshold P.9708 for time P.9709.
Type:
Latched warning
Related parameters:
P.9641
Nominal voltage (DC).
P.9711
Battery voltage hysteresis.
P.9712
Min battery voltage threshold.
P.9713
Min battery voltage delay.
To disable:
P.9713 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery voltage remains continuously
below to threshold P.9712 (percentage of the rated voltage P.9641) for time P.9713.
Type:
Warning
Related parameters:
P.9641
Nominal voltage (DC).
P.9711
Battery voltage hysteresis.
P.9714
Low battery voltage threshold.
P.9715
Low battery voltage delay.
To disable:
P.9715 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery voltage remains continuously
below to threshold P.9714 (percentage of the rated voltage P.9641) for time P.9715.