186
Technical Handbook
To disable:
P.0214 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Full
This protection is activated if the engine does not stop within the time set in P.0214 (since the
stop command).
Type:
Alarm
Related parameters:
P.0211 Number of starts attempts.
To disable:
-
Enabled in:
AUTO, TEST, REMOTE START
Override:
-
This protection is always enabled. It activates if the controller has performed P.0211
consecutive engine start attempts (auto start) without success.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the ACB status (function DIF.3002 -
“Status of ACB circuit breaker”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It activates only when ACB is commanded to open
and the status acquired is continuously “closed” for the time set.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the GCB status (function DIF.3001 -
“Status of GCB circuit breaker”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It activates only when GCB is commanded to open,
and the status acquired is cont
inuously “closed” for the time set.
Type:
Alarm
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs.
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START