Technical Handbook 93
This mode displays all the information on the measurements taken by the Gen-set control
module on the electric lines. You can scroll through the various pages using the LEFT and
RIGHT buttons.
Page M.01 (SYSTEM) displays a wiring diagram of the system. The system can be made up
by a maximum of four “sources”:
•
The plant battery.
•
The generator.
•
The loads.
•
The auxiliary source.
Each source is automatically hidden (together with its measurements and its circuit breaker) if
not configured (when the controller does not acquire its DC voltage nor its current). However,
it is possible to use the parameter P.0494 to force the controller to hide one or more sources.
For each source, the controller shows:
•
A symbol for the source:
o
The plant battery symbol shows the charge level of the plant battery. It fills
from the bottom to the top (if it is fully black battery charge is 100%, if it has
only borders the battery is fully discharged).
o
The symbol of the generator is in “reverse” if the engine is started and if the
generator is powered.
o
The symbol of the load is displayed in “reverse” if the loads are powered.
o
The symbol of the auxiliary source is solid if the auxiliary source is within the
tolerance range and flashing if the auxiliary source is missing or if it exceeds
the tolerance range.
•
A symbol for the circuit breaker. This symbol is hidden if the controller does not acquire
the feedback of the circuit breaker and if no outputs have been configured for its
commands. However, it is possible to use the parameter P.0494 to force the controller
to hide one or more circuit breakers. The symbol changes to show the real status
(opened/closed) of the circuit breaker (or its command if the feedback is not acquired).
The symbol blinks in case of difference between status and the breaker command.
•
The voltage (DC) and current measurements. The current measure is hidden if not
acquired or when the circuit breaker is opened. The voltage measure is hidden if not
acquired or when the related source i
s “absent”. However, it is possible to use the
parameter P.0494 to force the controller to hide the measures of one or more sources.
•
The power flow, shown by means an arrow (only if the related circuit breaker is
closed). The arrow points in the direction of the power flow.
This page shows a lot of information regarding the plant battery and its charge process:
•
Voltage (Vdc).
•
Current (Adc, positive during discharge).
•
Power (kW, positive during discharge).
•
Charge level (Ah).
•
Temperature (°C).
•
An estimation of the remaining hours to the end of the charge/discharge process.
During the charge cycle, it also shows:
•
The charge phase in progress (BULK, ABSORBTON, FLOAT, FLOAT END).
•
An estimation of the remaining time to the end of the current charge phase.
In the bottom, a graphical representation of the charge level is provided through a progress
bar (percentage).