Technical Handbook 35
The operator must first decide if the list of conditions must be evaluated as AND (all must be
checked) or as OR (it is enough that one condition is met).
You cannot have mixed AND/OR
logics (this can be done using digital virtual inputs; see below).
You can add up to 30 conditions. Each condition can be reversed individually: in the previous
figure, for instance, the controller will check that the digital input 3 and the digital output 8 are
both
inactive
. The following conditions can be added:
•
DI_XXX: logic states of all the digital inputs (physical or virtual).
•
DO_XXX: logic states of all the digital outputs.
•
AL_XXX: warnings/locks present.
•
ST_XXX: internal states of the controller.
•
AT_XXX: states concerning the thresholds on analogue measures (see par. 5.6.2).
The following table shows the list of the internal states available for the AND/OR logics.
Status
Description
ST_000
OFF_RESET
ST_001
MAN
ST_002
AUTO
ST_003
TEST
ST_004
AVVIAMENTO REMOTO
ST_008
Warnings
ST_009
Latched warnings
ST_010
Deactivations
ST_011
Alarms
ST_012
Not recognized warnings
ST_013
Not recognized latched warnings
ST_014
Not recognized deactivations
ST_015
Not recognized alarms
ST_016
Auxiliary source present (voltages/frequency)
ST_017
Auxiliary source absent or out of thresholds
ST_018
Delay for auxiliary source in thresholds
ST_019
Auxiliary source in thresholds
ST_020
Delay for Auxiliary source absent or out of thresholds