Manual – MOVIPRO® SDC with DeviceNet Interface
93
10
Explanation of the parameters
Parameterization of MOVIPRO
®
For a list of possible fault responses, refer to
P83x Fault responses
(page 117).
The following information is stored at the time of the fault and can be displayed in the
event of a fault:
• Status ("0" or "1") of the binary inputs/outputs
• Operating status of the inverter
• Inverter status
• Heat sink temperature
• Speed
• Output current
• Active current
• Unit utilization
• DC link voltage
• Hours of operation
• Enable hours
• Parameter set
• Motor utilization 1 and 2
P09x Bus diagnostics
P094 – P096
PO1 – PO3 set-
point
Displays the value currently transferred on the process data word in hexadecimal form.
P097 – P099 PI1 –
PI3 actual value
Displays the value currently transferred on the process data word in hexadecimal form.
10.4.3 P1xx Setpoints/ramp generators
P13x / P14x Speed ramps 1/2
P130 – P133 /
P140 – P143 ramp
t11 / t21 up/down
CW/CCW
P130 Ramp t11 up CW / P140 Ramp t21 up CW
P131 Ramp t11 down CW / P141 Ramp t21 down CW
P132 Ramp t11 up CCW / P142 Ramp t21 up CCW
P133 Ramp t11 down CCW / P143 Ramp t21 down CCW
Setting range: 0 – 2 – 2000 s
PO setpoint
Description
P094 PO1 setpoint
P870 Setpoint description PO1
(page 120)
P095 PO2 setpoint
P871 Setpoint description PO2
(page 120)
P096 PO3 setpoint
P872 Setpoint description PO3
(page 120)
PI setpoint
Description
P097 PI1 actual value
P873 Actual value description PI1
(page 120)
P098 PI2 actual value
P874 Actual value description PI2
(page 120)
P099 PI3 actual value
P875 Actual value description PI3
(page 120)
1
2
0
0
I