Manual – MOVIPRO® SDC with DeviceNet Interface
10
Explanation of the parameters
Parameterization of MOVIPRO
®
P562 Current limit
A
Setting range: 0 – 50 – 150 %
Current limitation that is permitted with operating frequency f
A
. There is a linear gradient
between current limitation A and current limitation B.
P563 Frequency B
Setting range: 0 – 10 – 104 Hz
Value for operating frequency f
B
.
P564 Current limit
B
Setting range: 0 – 80 – 200 %
Current limitation that is permitted with operating frequency f
B
. There is a linear gradient
between current limit B and current limit C.
P563 Frequency C
Setting range: 0 – 25 – 104 Hz
Value for operating frequency f
C
.
P566 Current limit
C
Setting range: 0 – 100 – 200 %
Current limit that is permitted between operating frequency f
C
and rated motor fre-
quency. The rated motor frequency is 50 Hz for star connection and 87 Hz for delta con-
nection. After startup with an Ex-e motor, the current limit C is approximately equal to
the rated motor frequency I
N
.
10.4.7 P6xx Terminal assignment
P601 – P604
Binary inputs
DIØ2 – DIØ5
The binary inputs can be programmed to the following functions:
AUTO
AUTO
AUTO
AUTO
AUTO
Function
Effect when
Effective with
inverter status
Fac-
tory-
set to
see
"0" signal
"1" signal
Inhib-
ited
Enabled
No function
–
–
–
–
DIØ2
DIØ3
DIØ4
DIØ5
Enable/stop
Stop on t13/t23
Enable
no
yes
P13x / P14x
(page 93)
CW/halt
Stop on t11/t21 or t12/
t22
Enable CW
no
yes
CCW/halt
Stop on t11/t21 or t12/
t22
Enable CCW
no
yes
n11/n21
n13/n23
External setpoints
only
n11/n21
n13/n23
no
yes
P16x / P17x
(page 95)
n12/n22
External setpoints
only
n12/n22
no
yes
Fixed setpoint swi-
tchover
Fixed setpoints of the
active parameter set
selected
Fixed setpoints of
the active parame-
ter set selected
yes
yes
Parameter set
switchover
1)
Parameter set 1
Parameter set 2
yes
no
Speed ramp
switchover
1. Ramp (t11/t21)
active
2. Ramp (t12/t22)
active
yes
yes
P13x / P14x
(page 93)
/External error
External error
-
no
yes
Error reset
Reset on positive edge ("0" to "1")
yes
yes
/Hold control
Hold control active
-
no
yes
P210
(page 98)
/Limit switch CW
Right limit switch
reached
Not reached
no
yes
/Limit switch CCW
Left limit switch
reached
Not reached
no
yes
0
0
I