Manual – MOVIPRO® SDC with DeviceNet Interface
5
Configuration examples in RSLogix 5000
Configuration and Startup on the DeviceNet Fieldbus
2. Define the following controller tags:
3. Create a rung to execute the "ReadParameter" command:
• For the contact, select the "ReadParameterStart" tag
• For message control, select the "ReadParameter" tag
4. Click on in the MSG command to open the “Message Configuration” window:
Choose “CIP Generic” as the “Message Type”. Fill the other fields in the following or-
der:
A Source Element = ReadParameterRequest.Index
B SourceLength = 12
C Destination = ReadParameterResponse.Index
D Class = 7
hex
E Instance = 1
F Attribute = 4
hex
G Service Code = e
hex
The service type is set automatically.