Manual – MOVIPRO® SDC with DeviceNet Interface
11
MOVIPRO
®
SDC error list
Service
81
Start condition
Immediate dis-
connection
0
Start condition error with "VFC
& hoist"
Only in "VFC & hoist"
mode:
The motor could not be
supplied with the cor-
rect amount of current
during the pre-magne-
tizing time:
•
Rated motor power
too small in relation
to rated inverter
power
•
Motor cable cross
section too small
•
Check startup data and
perform new startup, if
necessary.
•
Check connection between
inverter and motor
•
Check cross section of
motor cable and increase if
necessary
82
Open output
Immediate dis-
connection
0
Output open with "VFC &
hoist"
Only in "VFC & hoist"
mode:
•
2 or all output
phases interrupted
•
Rated motor power
too small in relation
to rated inverter
power
•
Check connection between
inverter and motor
•
Check startup data and
perform new startup, if
necessary.
84
Motor protec-
tion
Emergency
stop (P)
0
"Motor temperature emula-
tion" error
•
Motor utilization too
high.
•
I
N
-U
L
monitoring 1
triggered
•
P530 set later to
"KTY"
•
Reduce load
•
Extend ramps
•
Observe longer pause
times
•
Check P345/P346
•
Select a larger motor
2
Short circuit or open circuit in
the temperature sensor
3
No thermal motor model avail-
able
4
U
L
monitoring error
11
Temperature sensor short cir-
cuit
88
Flying start
Immediate dis-
connection
0
"Flying start" error
Only in "VFC n con-
trol" mode:
Actual speed > 6000
rpm when inverter
enabled
Enable not unless current
speed
≤
6000 rpm
94
EEPROM
checksum
Immediate dis-
connection
0
Power section parameters
Inverter electronics dis-
rupted, possibly due to
effect of EMC or a
defect.
Send unit in for repair.
5
Control unit data
6
Power section data
7
Invalid version of the configu-
ration data set
97
Copy error
Immediate dis-
connection
0
Parameter set upload is/was
faulty
•
Error during data
transmission
•
Memory can neither
be written nor read
•
Repeat copying process
•
Restore default setting
(P802) and repeat copying
process
1
Parameter set download to unit
cancelled
2
Not possible to adopt parame-
ters
98
CRC error
Immediate dis-
connection
0
"CRC via internal flash" error
Internal unit error
Flash memory defective
Send unit in for repair
99
IPOS ramp
calculation
Immediate dis-
connection
0
"Ramp calculation" error
Only in IPOS
plus
®
mode:
Positioning ramp is
sinusoidal or square
and an attempt is made
to change ramp times
and traveling velocities
with enabled inverter.
Rewrite the IPOS
plus®
program
so that ramp times and travel-
ing velocities can only be
altered when the inverter is
inhibited.
100
Vibration warn-
ing
Display error
(P)
0
Vibrations diagnostics warning Vibration sensor warn-
ing (see "DUV10A"
operating instructions)
•
Determine cause of
vibrations
•
Continue operation until
F101 occurs
101
Vibration error Rapid stop (P) 0
Vibration diagnostics error
Vibration sensor signals
fault
SEW-EURODRIVE recom-
mends that you remedy the
cause of the vibrations immedi-
ately
Error
Suberror
Code Designation
Response (P) Code Designation
Possible cause
Measure