92
Manual – MOVIPRO® SDC with DeviceNet Interface
10
Explanation of the parameters
Parameterization of MOVIPRO
®
P017 Work
Total of the active electrical energy the motor has consumed; storage cycle every 15
min.
P018 / P019 KTY
utilization 1 / 2
Display 0 %: Motor is not in operation at max. ambient temperature.
Display 110 %: Cut-off point of motor.
P02x Analog setpoints
P020 Analog input
AI1
Voltage (
−
10 V – +10 V) at analog input AI1 (020).
P03x Binary inputs of basic unit
P030, P032 –
P035 binary inputs
DI00, DI02 – DI05
Displays the current status of the input terminals DI00 and DI02 – DI05 and the current
function assignment. For possible terminal assignments, refer to
P601 – P604 binary in-
puts DIØ2 – DIØ5
(page 108).
P05x Binary outputs of basic unit
P050 Binary output
DB00
Displays the current status of the binary output on the basic unit with the the current
function assignment.
P07x Unit data
P070 Unit type
Displays the complete designation of the unit, e.g. PFA-MD0040B-5A3.
P071 Rated out-
put current
Displays the r.m.s. value of the rated output current.
P072 Encoder slot
option/firmware
Displays the installed encoder card and its program version.
P076 Basic unit
firmware
Displays the program version of the firmware used in the basic unit.
P078 Technology
function
Displays the currently set technology function.
"Standard": Setting for operating the inverter with the standard functions (positioning,
speed control, etc.).
P079 Unit version
Displays the unit version.
"Technology": Application modules and technology functions are available.
P08x Fault memory
P080 – P084 Fault
t-0 – t-4
There are 5 fault memories (t-0 – t-4). The faults are stored in a chronological sequence
with the most recent fault event being held in fault memory t-0. If there are more than 5
faults, the fault event of longest standing, stored in t-4, is deleted.
INFORMATION
The binary input DI00 is always assigned the function “controller inhibit”.