5
Electrical installation
Connection of MOVIMOT® MM../AND3/AZSK (connection option C)
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
33
5.5
Connection of MOVIMOT
®
MM../AND3/AZSK (connection option C)
Connection
of
MOVIMOT®
MM../AND3/
AZSK
(connection
option C)
The following figure shows the connection in MM../AND3/AZSK design:
0V
L3
N.C.
N.C.
N.C.
L1
3
1
2
4
24V
24V
0V
3
1
2
4
[1]
3
1
2
4
3
1
2
4
[3]
AS-Int
AS-Interface -
[4]
VO24
V0
PE
DI2
DI3
[2]
1
2
2
1
3
3
4
4
X02
X03
X01
YE
BK
BK
X02
X03
X01
PE
N.C.
L2
N.C.
45035997397817355
AZSK plug connector
[1]
X01:
M12 plug connector
(male, black)
1 24 V
24 V supply (AUX PWR)
2 N.C.
Not connected
3 0 V
Reference potential AUX PWR
4 N.C.
Not connected
[2]
X03:
M12 plug connector
(female, black)
1 VO24
24 V voltage supply for sensors
2 DI3
DI3 sensor input
3 V0
'
0 V reference potential for sensors
4 DI2
DI2 sensor input
5 PE
PE
[3]
X02:
M12 plug connector
(male, yellow)
1 AS-Int
AS-Interface signal cable +
2 0 V
Reference potential AUX PWR
3 AS-Interface -
AS-Interface signal cable -
4 24 V
24 V supply (AUX PWR)
AND3 plug connector
[4]
AND3 plug connector
(male)
1 N.C.
Not connected (reserved for N)
2 L2
L2 line connection
3 N.C.
Not connected
4 N.C.
Not connected
5 N.C.
Not connected
6 L3
Line connection L3
7 N.C.
Not connected
8 L1
Line connection L1
PE
PE
27792307/EN – 07/2022