6
Startup of MOVIMOT
®
with MLK.. in Easy mode
Supplementary notes for installation close to the motor
Compact Operating Instructions – MOVIMOT
®
MM..D with AS-Interface
64
6.8.4
Motor protection
INFORMATION
This chapter only applies to MM../AVSK design.
The connected motor must be equipped with a TH. SEW‑EURODRIVE recommends
wiring the TH via input DI2, see following figure.
•
Input DI2 must be monitored by an external controller.
•
As soon as input DI2 = "0", the external controller must switch off the drive (bit
DO0 and DO1 = "0").
TH
MOVIMOT
®
AS-
X6: 7
AS+
X6: 8
X6: 1,2
X6: 3,4
X6: 6
X6: 5
V0
VO24
DI2
DI3
When mounted close to the motor, input DI2 is no longer available for connecting ex-
ternal sensors.
6.8.5
Motor protection
INFORMATION
This chapter only applies to the following designs:
•
MM../AZSK
•
MM../AND3/AZSK
•
MM../AZZK
•
MM../AND3/AZZK
•
MM../AZFK
The inputs DI. are assigned to the sensor inputs. No TH can be connected to the
MOVIMOT
®
inverter. Motor protection via TH is not possible.
The motor protection must be ensured via the thermal motor protection model of the
MOVIMOT
®
inverter as follows:
•
Start up the MOVIMOT
®
drive in Expert mode. See chapter "Startup of MOVIMOT
®
with MLK.. in Expert mode".
•
Set the following parameters according to the following table:
Parameters
Required settings
No.
Index
Subindex Designation
340
8533
0
Motor protection
1: ON
347
10096 32
Motor cable length
Motor cable length in [m]
27792307/EN – 07/2022