Ambient temperature
The devices are suitable for an ambient temperature of 40 °C, max. 60 °C respectively
55 °C (Z.9 only) with derated output current. To determine the output current rating at
higher than 40 °C, the output current should be derated 3.0 % per °C between 40 °C
and 60 °C respectively 55°C (Z.9 only).
•
Only use certified units with a limited output voltage (V
max
= DC 30 V) and limited
output current (I ≤ 8 A) as an external DC 24 V voltage source.
•
The UL certification only applies for the operation on voltage supply systems with
voltages to ground of max. 300 V. The UL-certification does not apply to operation
on voltage supply systems with a non-grounded star point (IT systems).
27792307/EN – 07/2022