Details about Function Parameters
91
F5-11
Output Functions of T10/Y7
(Extension Output)
Factory
Settings
32
Modification
×
F5-12
Output Functions of T11/Y8
(Extension Output)
Factory
Settings
33
Modification
×
Setting
Range
0
~
59; refer to the following table of definitions of digital output functions
Related Monitoring Parameters: FU-27, FU-28, FU-30 and FU-31(Digital Output Terminal
Status)
Table of Definitions of Digital Output Functions
0: Inverter ready for operation
±1: Inverter in operation
±2: Frequency attained
±3: Output of Monitor 1
±4: Output of Monitor 2
±5: Output of Monitor 3
±6: Fault output
±7: Motor overload
±8: Motor overload
±9: Undervoltage lockout
±10: Shutdown by external fault
±11: Fault self-reset in process
±12:Instantaneous
poweroff/poweron in process
±13: Alarm output
±14:Anticlockwise operation in
process
±15: Shutdown in process
±16: Operation disabled
±17: Under control of control
panel
±18: Output at a preset time
±19: Upper frequency limit
enabled
±20: Lower frequency limit
enabled
±21: Power generation in
process
±22: PC Digital Quantity 1
±23: PC Digital Quantity 2
±24: Motor #1 in
variable-frequency operation
±25: Motor #1 in line
frequency operation
±26: Motor #2 in variable
frequency operation
±27: Motor #2 in line
frequency operation
±28: Motor #3 in
variable-frequency operation
±29: Motor #3 in line
frequency operation
±30: Motor #4 in variable
frequency operation
±31: Motor #4 in line
frequency operation
±32: Motor #5 in variable
frequency operation
±33: Motor #5 in line
frequency operation
±34: X1
±35: X2
±36: X3
±37: X4
±38: X5
±39
:
X6
±40: X7 (Extension terminal)
±41: X8 (Extension terminal)
±42: X9 (Extension terminal)
±43: X10 (Extension terminal)
±44: X11 (Extension terminal)
±45: FWD
±46: REV
±47: Pump ready for
acceleration
±48: Pump ready for
deceleration
±49: Startup signal of auxiliary
starter
±50: Working terminal of
sleeping pump
±51: Indication for sleeping
operation
±52: Water shortage in suction
pool
±53: Abnormal closing of
contactor
±54: Drainage pump control
±55: Water injection valve
control for Pump #1
±56: Air vent valve control for
Pump #1
±57: Water injection valve
control for Pump #2
±58: Air vent valve control for
Pump #2
±59: Firefighting patrol in
operation
±60: AI1>AI3
Refer to the following details about the digital output function:
NOTE:
When the signal is effective, if the value is positive, the relay will be closed and Terminal
Y willl be connected to the transistor. If the value is negative, the relay will be open and Terminal
Y will be disconnected from the transistor.
0:
Inverter ready for operation:
The energized contactor has been closed. There is no fault.
1:
Inverter in operation:
The inverter is in operation.
Summary of Contents for SB200 Series