Details about Function Parameters
86
Terminal #1(F3-02) #2
(F8-30)
#3
(F8-31)
#4 (F8-32)
Motor Option 1
0
1
0
1
Motor Option 2
0
0
1
1
In the constant-pressure water supply mode, the rated current will be automatically selected for the
corresponding pumps to achieve overload protection values. When the digital input is set as 43 and 44,
the corresponding function is Pump Disabled Options
45
~
49: Pump Disabled:
After the corresponding water pump disablement signal is inputted,
an overhaul of an abnormal pump shutdown will be carried out. This function applies
primarily to water pump overhaul and no manual shutdown of system operation is required.
After the water pump is overhauled, repeal the disablement command and the pump will be
automatically started.
50
~
51: Check of Waste Water Pool Level:
Refer to the description of F8-03 on Page 72.
52
~
53: Water Level Control Detection Signal:
When the water supply mode is switched to
water level control, the water pump will be started up or shut down according to the water
level detection signal. When the lower limit signal is ineffective, the pump will be started;
when the upper limit signal is effective, the pump will be shut down.
54: Signal of Firefighting System in Operation:
When this signal is effective, the main pumps
and auxiliary pumps are started and run at the max. capacity. No constant pressure control
is executed. After the firefighting command is repealed, the system will be automatically
restored to the original operation status.
55
~
57: Priority Pump Startup Options:
When the tens digit of F8-39 is 0, the pump to be
started first may be directly designated via the control terminal. The priority mode is only
effective for a system in standby, constant-pressure mode.
Priority Pump
Startup Option 3
Priority Pump
Startup Option 2
Priority Pump
Startup Option 1
Sequence of Priority
0 0 0
#1
Water
Pump
0 0 1 #1
Water
Pump
0
1 0
#2
Water
Pump
0
1
1 #3
Water
Pump
1 0 0
#4
Water
Pump
1 0 1 #5
Water
Pump
F4-13
Terminal Operation Mode
Factory
Settings
1
Modification
×
Summary of Contents for SB200 Series