Installation and Wiring
19
SB200-18.5T4—22T4 100
10
SB200-220T4
630
210
SB200-30T4 125
16
SB200-250T4—280T4
850
240
SB200-37T4 160
25 SB200-315T4
1000
300
SB200-45T4—55T4 200
35 SB200-375T4—400T4
1500
400
Refer to the following drawing for fundamental wiring required for operation
x
Short lug
Braking resistor
Applied to 22kW and
below only
R
S
T
R
S
T
PE
High-voltage
indication
U
V
W
M
3~
SB200
inverter series
Multifunctional
relay output
1TB
1TC
1TA
2TB
2TC
2TA
3TB
3TA
4TB
4TA
5TB
5TA
Multifunctional collector
open-circuit output
Pulse frequency output
Multifunctional analog output
AO1
AO2
GND
Y1
Y2/PFO
GND
Y2/PFO
CJ3
AI3
mA
V
CJ1
AI1
mA
V
CJ5
AO2
mA
V
mA
V
CJ4
AO1
mA
V
Pulse frequency input
Shielded layer
Potentiometer
Transducer
RS-485
interface
X1
X2
X3
X4
X5
X6/PFI
FWD
REV
GND
X6/PFI
+10V
AI1
GND
AI2
AI3
24V
485+
485-
P1
P+
DB
N-
CJ2
AI2
Applied to 30kW and above
only; The installation of a DC
reactor requires the removal
of the jumper between P1
and P+
DC reactor
3-phase input
380V 50/60Hz
Mul
tifunctio
n
al di
gital
input
Braking
resistor
Note: Copper-core conductors of 1mm² are recommended for connecting wires of the control terminal.
Main Circuit terminal function notes:
Terminal
Code
Terminal Name
Description
R/S/T
Power supply terminal
Connected to the 3-phase 380V power supply
U/V/W
Inverter output terminal
Connected to the 3-phase motor
P1/P
+
DC reactor terminal
Connected to the external DC reactor (A jumper is used
for connection if a reactor is inapplicable)
P
+
/N
-
DC output terminal
Used for connection to a braking unit
DB
Braking output terminal
A braking resistor connects P+ to DB
PE Earth
terminal
The earth terminal on the inverter enclosure must be
earthed