Details about Function Parameters
68
It is used for calibration for a frequency setting by analog input or PFI.
F0-07 “Upper Frequency Limit”/F0-08 “Lower Frequency Limit”: Limits for the final frequency
settings.
F0-09
Direction Lock
Factory
Setting
s
0
Modification
○
Setting
Range
0: Both clockwise
direction and
anticlockwise direction
are applicable
1: Clockwise direction
lock
2: Anticlockwise direction
lock
It is recommended that the direction lock be used only for a single-direction rotation.
If a direction change is required by turning
on the control panel, the hundreds digit of
FC-01 must be set as 1 or 2.
F0-10
Parameter Write Protection
Factory
Setting
s
0
Modification
○
Setting
Range
0: Write protection inapplicable; all parameters are subject to rewriting except read-only
parameters
1: No parameter is subject to rewriting except F0-00 “Digital Frequency Settings”,
F7-04 “PID Digital Settings” and this parameter
2: No parameter is subject to rewriting except this parameter
This function prevents modification of parameters by error.
F0-11
Parameter Initialization
Factory
Setting
s
00
Modification
×
Setting
Range
11: Initialization 22: Initialization applicable to all parameters except
communication parameters NOTE: The parameter automatically changes to 00
upon completion of initialization
Parameter initialization restores a parameter to factory settings and the fault logs are not restored
(Fault logs may be cleared by FP-20).
F0-12
Parameter Copying
Factory
Setting
s
00
Modification
×
Setting
Range
11: Parameters are uploaded from the
inverter to the panel
33: Conformity of the control panel to
the inverter parameters is verified
After verification, the parameter
automatically changes to 00
22: Parameters are downloaded from the
control panel to the inverter
44: Parameters stored in the control panel
are cleared