![Senlan SB200 Series User Manual Download Page 12](http://html1.mh-extra.com/html/senlan/sb200-series/sb200-series_user-manual_1239807012.webp)
Product Specification
8
2. Product Specification
2.1. Universal Technical Specification of SB200 Inverter Series
Item
Description
Rated Voltage/Frequency
3-phase, 380V; 50/60Hz
Input
Range
Voltage: 320-420V; voltage unbalance:<3
%
;
frequency: 47-63Hz
Output Voltage
3-phase; 0v-input voltage; error: below 5%
Output Frequency
0.00-650.00Hz
Overload Capacity
110% of rated current; 1 minute
Frequency Resolution
Digital setting: 0.01Hz; analog setting: 0.1% of max
frequency
Output Frequency Accuracy
Analog setting: ±0.2
%
of max frequency (25±10
℃
);
digital setting: 0.01Hz (-10—+40
℃
)
Command Execution Channel
Settings may be configured via the control panel,
control terminal or communication port. Switching is
enabled via the terminal
Frequency Setting Channel
Control panel, communication port, UP/DOWN
adjustment, AI1, AI2, AI3 or PFI
Auxiliary Frequency Setting
Flexible auxiliary frequency micro-adjustment and
frequency setting synthesis
Torque Elevation
Auto/manual torque elevation
V/F Curve
Customizable V/F curves, linear V/F curves and 5
torque reduction characteristic curves
Jogging
Jogging frequency range: 0.10-50.00Hz; jogging
acceleration/deceleration time: 0.1-60.0s
Auto Energy Saving
Load-based auto V/F optimization, capable of auto
energy saving
AVR
When the grid voltage fluctuates within a specified
range, the inverter can automatically maintain a
constant output voltage
Auto Carrier Regulation
Auto carrier regulation based on load characteristics
and ambient temperature
Random PWM
Tone adjustment for an operating motor
Instantaneous Power Failure
Solution
Uninterrupted operation via busbar voltage regulation
in the event of an instantaneous power failure
DC Braking
Braking time: 0.0-60.0s; braking current: 0.0-100.0
%
of rated current
PFI
Max input frequency: 50kHz
PFO
Connector open circuit-type pulse square wave signal
output; programmable
Analog Input
3-channel analog signal input; options for
voltage/current modes; capable of positive/negative
input
Analog Output
2-channel analog signal output; options for 0/4-20mA
or 0/2-10V; programmable
Digital Input
8-channel multifunctional digital input
Digital Output
2-channel multifunctional collector open-circuit
output; 5-channel multifunctional relay output
Output
Communication
Inbuilt RS48S communication interface supporting
Modbus protocol and USS commands
Feature
Process Identification
Two PID parameter systems and multiple correction
modes