Lists of function parameters
48
Paramete
r
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
F7-12
Sampling Period
0.001—10.000s
0.010s
○
127
F7-13
Ultimate Deviation
0.0—20.0%; PID settings is taken as 100%
0.0%
○
127
F7-14
Set Value
Increase/Decrease Time
0.00—20.00s
0.00s
○
128
F7-15
PID Adjustment
Characteristics
0: Positive action
1: Negative action
0
×
128
F7-16
Integral Control Options
0: No integral action
1: Integral action
1
×
110
F7-17
PID Upper Amplitude
Limit
F7-18“PID Lower Amplitude Limit”—100.0%
100.0%
○
129
F7-18
PID Lower Amplitude
Limit
-100.0%
-
F7-17“PID Upper Amplitude
Limit”
0.0%
○
129
F7-19
PID Differential
Amplitude Clipping
0.0
-
100.0%; clipping of the upper/lower
amplitude limits of differential components
5.0%
○
129
F7-20
PID Preset Value
-F7-18
-
F7-17
0.0%
○
129
F7-21
PID Preset Value Hold
Time
0.0
-
3,600.0s
0.0s
×
129
F7-22
Multi-PID Setting 1
1.00
F7-23
Multi-PID Setting 2
2.00
F7-24
Multi-PID Setting 3
3.00
F7-25
Multi-PID Setting 4
4.00
F7-26
Multi-PID Setting 5
5.00
F7-27
Multi-PID Setting 6
6.00
F7-28
Multi-PID Setting 7
-F7-03
-
F7-03
7.00
○
130
F8: Dedicated Water Supply Functions
Paramete
r
Name
Setting Range and Description
Factory
settings
Mod
ificat
ion
Page
F8-00
Water Supply Function
Modes
0: Water supply function is not selected
1: Common PI-regulated constant-pressure
water supply
2: Water level control
3: Pumps are started on by one in the sequence
based on water pump capacity
4: Firefighting water supply
0
×
130