Details about Function Parameters
65
6. Details about Function Parameters
6.1. F0: Basic Parameters
F0-00
Digital Frequency Settings
Factory
Settings
50.00Hz
Modification
○
Setting
Range
0.00Hz
~
F0-06“Max. Frequency”
F0-01
Main Setting Channel for
Normal Operation
Factory
Settings
0
Modification
○
0: F0-00 adopts digital settings via
the control panel adjustment (
and
)
2: UP/DOWN adjustment 3:
AI1
1: Communication settings; F0-00 is used for
initial value
4: AI2 5: AI3
Setting
Range
6: PFI 7: Panel potentiometer (applicable only to SB-PU03)
Refer to the following figures for frequency channel settings:
+
+ +
F0-00 digital settings
Communication
reference
UP/DOWN Value
AI1
AI2
AI3
PFI
Main reference
select
( for normal
operation)
Hig
h
pr
io
ri
ty
/L
ow
pr
io
ri
ty
F1-06
Jog frequencyl
Process PID
Multi-speed
Main reference frequency
No auxilairy
AI1
AI2
AI3
PFI
Jog Command
Reference frequency
before limitation
F0-05
Auxiliary
channel gain
Digital input32
PID Correction
(F7-00=2)
F0-04
Panel potentiometer
AI1
Digital Input 11
F0-00 digital settings
UP/DOWN Value
Auxilairy reference
frequency
The inverter has four operation modes with the following priority levels (from high to low): jogging,
process identification (PID), multi-speed and normal operation. For instance, if the multi-speed mode is
effective in a normal operation, the main frequency settings will depend on the multi-band frequency.
The main settings of normal operation may be selected via F0-01 “Main Setting Channel for
Normal Operation”. Forced switching may be executed by digital input 11(“Switching of
frequency settings to AI1”). Refer to Page 53 for details.
Define the auxiliary setting channel via F0-04 “Auxiliary Setting Channel Options”, or disable it
via digital input 32 “auxiliary channel disabled”. Refer to Page 53 for details
If F7-00 “PID control function options” is set as 2, the pre-ramp frequency settings may be