Installation of an approved safety valve
with opening overpressure
set to 2,5 bar is mandatory in closed systems. Safety and expansion
conduits must not have any kind of block elements.
It is necessary to
install the deaerating valve
. When filling the boiler
and the radiator system it is necessary to open the mixing valve, if one had
been installed; adequately deaerate the boiler and the heating system.
The mixing valve
(
7
–
figure 9
)
maintains the boiler temperature at
minimum the 60
C, thus preventing the boiler from condensation
. If
one had not been installed, it is necessary to ensure firing conditions that
will prevent boiler condensation.
Condensation may appear at the
beginning of the firing process or due to insufficient feeding.
Pipeline thermostat which activates the circulation pump must not
be adjusted to values lower than 60
C !
4.6.1. COOKER THERMAL PROTECTION
When connecting the cooker to the central heating system it is
necessary to install the safety thermal valve.
It shall be installed on the
cooker rear side to R3/4’’ connection point
– inner thread
figures10-13
.
Water outlet into the sewer
(or SW tank
– sanitary water) is connected
to connection point:
R3/4'' (7)
-
figure 10
, OR
R1/2'' (7)
-
figure 11
, OR
R3/4'' (8)
-
figure 12
.
The sensor
(probe)
of the safety thermal
valve
is connected to the
connection point (5)
broken line in
figures 10-13.
The central heating system must have its own separate
thermo-
manometer
!
THE BOILER MUST NOT BE USED WHEN EMPTY OF WATER !