background image

PA-02

PID feedback 

source

Default

 : 

0

0: PA-01 setting   
0: Ai1                 1: Ai2    
2: AI3/panel potentiometer   
3: AI1-AI2         4

  : Pulse setting (X6)

5: Communication given 
6: AI1+AI2        7:MAX(|AI1|, |Ai2|)
8:MIN(|AI1|, |AI2|)

 

 

The feedback amount of the process PID is also a relative value, and the 

setting range is 0.0% to 100.0%.

   This  parameter  is  used  to  select  the  feedback  signal  channel  of  the 
process PID.

PA-03

PID action direction

Default

 : 

0

0: Forward action
1: Reverse action

   Forward  action:  When  the  PID  feedback  signal  is  less  than  the  given 
amount, the inverter output frequency rises. Such as winding tension control 
occasions.

 

This  function  is  affected  by  the  reverse  direction  of  the  multi-function 

terminal PID (function 35), so you need to pay attention to it during use. 

 

Reverse action: When the feedback signal of the PID is less than the given 

amount, the output frequency of the inverter decreases. Such as unwinding 
tension control occasions.

PA-04

PID given feedback range

Default

 : 

1000

0

65535

 

 

PID given feedback range is a dimensionless unit for the PID given display 

U0-15 and the PID feedback display U0-16. The relative value of the given 
feedback of the PID is 100.0%, corresponding to the given feedback range 
PA-04. For example, if PA-40 is set to 2000, when the PID is given 100.0%, 
the PID given display U0-15 is 2000

PA-05

Proportional gain Kp1

0.0

100.0

 

Default

20

PA-06

Integration time Ti1

0.01s

10.00s

Default

1s

PA-07

Derivative time Td1

Default

2.00s

0.000s 10.000s

User Manual

138

User Manual

139

 

Determine the adjustment strength of the entire PID regulator, the larger 

the Kp1, the greater the adjustment intensity. The parameter 100.0 indicates 
that when the deviation between the PID feedback amount and the given 
amount is 100.0%, the adjustment range of the PID regulator to the output 
frequency command is the Maximum frequency.
 

Integration time Ti1: Determines the strength of the PID regulator integral 

adjustment.  The  shorter  the  integration  time,  the  greater  the  adjustment 
intensity. The integration time means that when the deviation between the 
PID feedback amount and the given amount is 100.0%, the integral regulator 
continuously adjusts through the time, and the adjustment amount reaches 
the Maximum frequency. 

   Proportional gain Kp1:

 

Derivative  time  Td1:  Determines  the  strength  of  the  PID  regulator's 

adjustment  to  the  rate  of  change  of  the  deviation.  The  longer  the 
differentiation time, the greater the adjustment intensity. The derivative time 
means that when the feedback amount changes by 100.0% during this time, 
the  adjustment  amount  of  the  differential  regulator  is  the  Maximum 
frequency. 

 

The  set  target  amount  of  the  process  PID  is  a  relative  value,  and  the 

setting range is 0.0% to 100.0%. The feedback amount of the same PID is 
also the relative amount, and the role of the PID is to make the two relative 
quantities the same

 

This parameter is used to select the target channel for the process PID.

PA-08

PID reverse cutoff frequency

Default : 2.00Hz

0.00

Maximum 

frequency

 

In  some  cases,  only  when  the  PID  output  frequency  is  negative  (the 

inverter reverse rotation), it is possible for the PID to control the given amount 
and  the  feedback  amount  to  the  same  state,  but  the  excessive  reverse 
frequency is not allowed for some occasions. PA-08 is used to determine the 
upper limit of the inversion frequency.

PA-09

PID deviation limit

Default 0.0%

0.0%

100.0%

   P When the deviation between the PID given amount and the feedback 
amount is smaller than PA-09, the PID stops the adjustment action. In this 
way, the output frequency is stable when the deviation from the feedback is 
small, which is effective for some closed-loop control applications. 

PA-10

PID differential limiting

Default 0.10%

0.00%

100.00%

 

In the PID regulator, the function of the differential is relatively sensitive, 

and it is easy to cause the system to oscillate. For this reason, the role of the 
PID differential is generally limited to a small range, and the PA-10 is used to 
set the range of the PID differential output.

Chapter 6

Chapter 6

Summary of Contents for ATSEL FD300

Page 1: ...ww selec europe com www selecaustralia com Selec USA Selec GmbH Selec Australia Selec Controls Pvt Ltd EL 27 1 Electronic Zone TTC Industrial Area MIDC Mahape Navi Mumbai 400710 INDIA Tel 91 22 4141 8...

Page 2: ...t Please ensure to turn off the power when wiring The AC power cord must never be connected to the inverter output terminals U V W The inverter must be properly grounded There is a high voltage circui...

Page 3: ...ection PA Process control PID function PB Swing frequency fixed length and counting PC Multi segment instruction and simple PLC function PP User password A0 Torque Control Function A5 Control optimiza...

Page 4: ...braking DC braking frequency 0 00 Hz max frequency Braking time 0 0 100 0s Braking trigger current value 0 0 100 0 JOG control JOG frequency range 0 00Hz 50 00 Hz JOG acceleration deceleration time 0...

Page 5: ...t terminal Standard 5 digital input DI terminals one of which supports up to 100 kHz high speed pulse input 2 analog input AI terminals support 0V 10 V voltage input or 0 mA 20 mA current input Expand...

Page 6: ...m 100mm UP Right CONVERTER CONVERTER CONVERTER User Manual User Manual Chapter 2 Chapter 3 7 6 Installation size Power level 15kw 18 5 30kw 37kw 50mm 300mm 50mm 200mm 20mm 100mm A B WIRING In order to...

Page 7: ...nnect a magnetic contactor MC in series to cut off the power supply when the inverter protection function is activated the R C surge absorber is required at both ends of the electromagnetic contactor...

Page 8: ...B2 terminal is connected to the braking resistor there is B1 B2 terminal indicates that the inverter has built in braking unit 3 3 4 Inverter Grounding Terminal PE For safety and noise reduction the g...

Page 9: ...ire 485 Positive signal 485 Communi cation 485 Negative signal KEYPAD OPERATION 4 1 Description of the keyboard panel Keyboard panel RUN When the light is off the inverter is in the stop state When th...

Page 10: ...lect the function code Set the value of the function code Level I menu Level II menu Level III menu Example An example of changing the function code P3 02 from 10 00 Hz to 15 00 Hz black mark indicate...

Page 11: ...Output current Bit7 Input status LED Running display parameters2 LED Stop display parameter P7 04 0000 FFFF Bit4 Remaining running time Bit6 AI2 Pre correction voltage V Bit0 PID Feedback Bit7 AI3 Pre...

Page 12: ...d control mode selection Run command source selection Main frequency source X selection Preset frequency 0 00Hz Maximum frequency P0 10 50 00Hz Rotation direction 0 Maximum frequency 50 00Hz 500 00Hz...

Page 13: ...eration time base frequency P0 26 0 running frequency 1 setting frequency 0 Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address P0 27 Single digit Operation panel command bind...

Page 14: ...c auto tuning 2 Complete auto tuning 3 Static full auto tuning 0 Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address P2 Motor vector control parameter P2 00 Fun ction Code Par...

Page 15: ...equency P1 04 0 00Hz 0 0 100 0 0 0 V F Slip compensation gain 0 0 200 0 0 0 0 200 64 V F oscillation suppression gain 0 100 Oscillation suppression mode selection 0 4 3 Voltage source for V F separati...

Page 16: ...Setting range Default Prope rty Modbus Address P4 Multi functional inputs parameters P4 00 Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address X1 Terminal function selection 1...

Page 17: ...eration prohibition 22 PID pause 23 PLC reset 24 swing frequency pause 25 counter input 26 Counter reset 27 Length count input 28 Length reset 29 Torque control prohibited 30 Pulse frequency input 32...

Page 18: ...election the same as above Hundreds AI3 is lower than the minimum input setting selection the same as above Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address Unit s digit X1...

Page 19: ...eady to RUN 16 AI1 AI2 17 Frequency upper limit reached 18 Frequency lower limit reached no output at stop 19 Under voltage status output 20 Communication setting 23 Zero speed running 2 having output...

Page 20: ...imum frequency 0 00Hz P6 12 Waiting time of stop DC braking 0 0s 100 0s 0 0s P6 13 Stop DC braking current 0 100 0 P6 14 Stop DC braking time 0 0s 100 0s 0 0s P6 15 Brake use ratio 0 100 100 P6 18 Spe...

Page 21: ...2 Hz Bit4 Remaining running time Bit5 AI1 pre correction voltage V Bit6 AI2 pre correction voltage V Bit7 AI3 pre correction voltage V Bit8 Linear speed Bit9 Current power on time Hour Fun ction Code...

Page 22: ...ion 0 P8 19 Frequency detection value FDT1 0 00Hz Maximum frequency 50 00Hz P8 20 Frequency detection hysteresis value FDT1 0 0 100 0 FDT1 5 0 P8 21 Frequency arrival detection width 0 0 100 0 Maximum...

Page 23: ...Wake up frequency P8 49 0 00Hz P8 52 Dormant delay time 0 0s 6500 0s 0 0s P8 53 Current running time reached 0 0Min 6500 0Min 0 0Min P8 54 Output power correction coefficient 0 00 200 0 100 0 Paramet...

Page 24: ...t phase loss protection option Tens place Contactor suction protection option 0 Disabled 1 Enabled 0 no fault 1 Reserved 2 accelerated overcurrent 3 Deceleration over current 4 Constant speed over cur...

Page 25: ...ace Input phase loss Err12 as above Hundreds place Output phase loss Err13 as above Thousands place External fault Err15 is the same as above Ten thousand communication abnormality Err16 is the same a...

Page 26: ...s stop non stop integral coefficient Ki 0 100 30 P9 73 Instantaneous stop and stop motion deceleration time 0 300 0s 20 0s Parameter Name Setting Range Default Prope rty Modbus Address Fun ction Code...

Page 27: ...aches the limit 0 Continue to integrate 1 Stop integral operation 0 0 PA 25 PID integral attribute 00 PA 26 PID feedback loss detection value 0 0 PID feedback loss detection time 0 0s 20 0s 0 0s PA 28...

Page 28: ...0 0 PC 12 Multi segment instruction 12 0 0Hz P0 10 0 0 PC 13 Multi segment instruction 13 0 0Hz P0 10 0 0 PC 14 Multi segment instruction 14 0 0Hz P0 10 0 0 PC 15 Multi segment instruction 15 0 0Hz P0...

Page 29: ...0s h 6553 5s h 0 0s h 6553 5s h 0 0s h 0 0s h 0 0s h PC 37 PC 39 PC 41 0 3 0 3 0 3 0 0 0 Section 9 acc and dec time selection Section 10 acc and dec time selection Section 11 acc and dec time selectio...

Page 30: ...Prope rty Modbus Address Fun ction Code PE 00 User function code 0 U3 17 PE 01 User function code 1 U3 16 PE 02 User function code 2 P0 00 Res erved Reserved Reserved PE 28 User function code 28 P0 0...

Page 31: ...depth 0 Invalid 1 10 Random PWM depth 0 A5 04 Rapid current limit 0 Invalid 1 Valid 1 A5 05 Current detection compensation 0 100 0 A5 06 Under voltage threshold 60 0 140 0 100 0 A5 07 SVC optimization...

Page 32: ...ction Code Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address AC AIAO checking Fun ction Code Parameter Name Setting range Default Prope rty Modbus Address AC 00 AI1 measured...

Page 33: ...ut power kW U0 06 Output torque 200 0 200 0 Display inverter output torque during operation U0 07 Input terminal status 0 32767 Input status X1 X9 corresponds to Bit0 Bit8 U0 08 Output terminal status...

Page 34: ...us machine rotor position U0 34 Motor tem perature value 1 Display motor temperature value U0 35 Target torque 0 1 Display target torque U0 36 Rotational position 1 Display the position of the rotatio...

Page 35: ...command channel LED off 1 terminal command channel LED is lit 2 Communication command channel LED flashing Default 0 1 Terminal command channel L R is on which is controlled by the multi function inpu...

Page 36: ...When the auxiliary frequency source Y is used as an independent frequency reference channel X to Y switching its usage is the same as that of the main frequency source X P0 03 Note when the auxiliary...

Page 37: ...requency source Y is used as the target frequency 2 Take the maximum of the absolute value of the main frequency X and the auxiliary frequencyYas the target frequency the offset frequency is set by P0...

Page 38: ...temperature 0 no 1 yes Default 1 When the inverter detects that its own temperature is high it automatically reduces the carrier frequency to reduce the temperature rise of the inverter When the tempe...

Page 39: ...rminal selection is subject to P0 25 Acceleration Deceleration time base frequency 0 Maximum frequency P0 10 1 Set frequency 2 100Hz Default 0 Acceleration deceleration time refers to the acceleration...

Page 40: ...l automatically modify the P1 06 P1 10 parameter values and restore these five parameters to the common standard Y series motor parameters If the asynchronous motor cannot be tuned at the site you can...

Page 41: ...loop integration time 2 0 01s 10 00s Default 1 00s Switchover frequency 2 P2 02 Maximum frequency Default 10 00Hz P2 Vector control parameter P2 function code is valid only for vector control and inv...

Page 42: ...Pulse setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full scale of the 1 7 option corresponds to P2 10 Default 0 Digital setting of torque upper limit in speed control mode 0 0 200 0...

Page 43: ...centrifugal loads such as fans and pumps 10 V F complete separation mode At this time the output frequency of the inverter is independent of the output voltage the output frequency is determined by t...

Page 44: ...ferent from the target value the gain needs to be fine tuned appropriately V F Over excitation gain 0 200 Default 120 P3 10 During the deceleration the over excitation control can suppress the rise of...

Page 45: ...ils see the introduction of the PAgroup PID 4 Pulse setting the voltage reference is given by the terminal pulse 5 ulti segment command when the voltage source is a multi segment command set the P4 gr...

Page 46: ...stall current exceeding the rated frequency fs fn k Limit Cur If the bus voltage exceeds the overvoltage stall point of 760V indicating that the electromechanical system is already in the power genera...

Page 47: ...frequency is incremented or decremented when the frequency is given by the external terminal When the frequency source is set to digital setting the set frequency can be adjusted up and down 7 Termin...

Page 48: ...utton function on the keyboard 37 Command source switchover terminal 2 Used for switching between terminal control and communication control If the command source is selected as the terminal control t...

Page 49: ...Multi segment instruction 15 PC 15 ON ON ON ON Schedule 2 Acceleration deceleration time selection terminal function description When the frequency source is selected as multi speed 100 0 of function...

Page 50: ...If the input terminal is susceptible to interference and cause malfunction increase this parameter to enhance the anti interference ability However this parameter increase will cause the X terminal to...

Page 51: ...se refer to the description of each part The following illustrations are for two typical settings When the analog input is a current input the 1mA current is equivalent to 0 5V The above function code...

Page 52: ...nding value 100 0 100 0 Default 100 0 Pulse input filtering time 0 00s 10 00s Default 0 10s This group of function codes is used to set the relationship between the multi function terminal X6 pulse in...

Page 53: ...mode of the digital input terminal 0 Positive logic the corresponding terminal is valid when connected to COM and the disconnection is invalid P5 Output terminal The inverter comes standard with one...

Page 54: ...ruction When the inverter runs and the output frequency is 0 the ON signal is output This signal is OFF when the drive is in the stop state 18 Frequency lower limit reached no output at stop When the...

Page 55: ...1 2 times the rated voltage of the inverter 6 PULSE input 0 01kHz 100 00kHz 7 AI1 0V 10V 8 AI2 0V 10V or 0 20mA Set value Function Function corresponding to pulse or Analog output 0 0 100 0 9 AI3 0V 1...

Page 56: ...the pre excitation time is not 0 the pre excitation is restarted first which can improve the dynamic response performance of the motor 0 Direct start if the DC braking time is 0 the inverter will star...

Page 57: ...er Acceleration Deceleration mode Default 0 P6 07 0 Linear acceleration and deceleration 1 S curve acceleration and deceleration A 2 S curve acceleration and deceleration B The output frequency is inc...

Page 58: ...op DC braking time 0 0s 100 0s Default 0 0s P6 11 P6 12 P6 13 P6 14 DC braking start frequency at stop When the inverter stops when the running frequency decreases to this frequency DC braking starts...

Page 59: ...y can be set by this function code This key can be used to switch between stop and run 3 Forward jog through the keyboard JOG REV Key to achieve forward jog 4 Reverse jog through the keyboard JOG REV...

Page 60: ...Frequency setting Bus voltage X input statue Output statue AI 1 voltage AI 2 voltage AI 3 voltage Count value 15 14 13 12 11 10 9 8 Length value PLC stage Overload speed PID setting Pulse input Reser...

Page 61: ...d to the direct start mode P 6 0 0 0 and the stop mode is fixed to the deceleration stop P6 10 0 Acceleration time 1 0 0s 6500 0s depend Deceleration time 1 0 0s 6500 0s depend Acceleration time 2 0 0...

Page 62: ...ng the same load The droop control means that as the load increases the output frequency of the inverter decreases so that when multiple motors are dragged by the same load the output frequency of the...

Page 63: ...requency relative to the frequency detection value P8 19 Figure 6 18 shows the function of the FDTfunction Figure 6 18 FDT level diagram Output frequency Hz FDT level Frequency arrival detection signa...

Page 64: ...2 is selected if the running frequency is greater than P8 25 the acceleration time 1 is selected During deceleration if the running frequency is greater than P8 26 the deceleration time 1 is selected...

Page 65: ...cted 0 1 300 0 motor rated current Default 200 0 P8 37 Output overcurrent detection delay time 0 00s 600 00s Default 0 00 When the output current of the inverter is greater than or exceeds the detecti...

Page 66: ...0 0 The fan is running during operation 1 The fan is always running Used to select the action mode of the cooling fan 0 The fan runs in the running state If the radiator temperature is higher than 40...

Page 67: ...fault 30 P9 04 Overvoltage stall protective voltage 120 150 Default 760V When the DC bus voltage exceeds the value of P9 04 Overvoltage stall protective voltage during deceleration of the inverter the...

Page 68: ...ic fault reset P9 12 Input phase loss protection option 0 Prohibited 1 Allowed Default 1 The inverter has the input phase loss protection function from the 18 5kW G type machine and above The power of...

Page 69: ...at the first failure Fault protection action selection 1 Default 00000 Fault protection action selection 3 BIT4 BIT3 BIT2 BIT1 BIT0 P9 28 P9 29 P9 30 P9 31 P9 32 P9 33 P9 34 P9 37 P9 38 P9 39 P9 40 P9...

Page 70: ...ailure voltage rise judgment time 000 0s 100 0s Default 0 5s Instantaneous power failure action judgment voltage 60 0 100 0 standard bus voltage Default 80 0 P9 60 P9 61 P9 62 This function means that...

Page 71: ...erter will continue to decelerate to 0Hz and stop until the inverter issues the start command again 2 The purpose of instantaneous stop is to ensure that when the power supply of the power grid is abn...

Page 72: ...nt The shorter the integration time the greater the adjustment intensity The integration time means that when the deviation between the PID feedback amount and the given amount is 100 0 the integral r...

Page 73: ...multi function terminal function selection should be set to 43 PID parameter switching terminal When the terminal is invalid select parameter group 1 PA 05 PA 07 When the terminal is valid select the...

Page 74: ...center and the running frequency is in the time axis As shown in Figure 6 31 the swing amplitude is set by PB 00 and PB 01 When PB 01 is set to 0 the swing is 0 At this time the swing frequency does...

Page 75: ...th PB 05 the output length reaches the ON signal During the fixed length control the length reset operation can be performed through the input terminal 28 In the application the corresponding input te...

Page 76: ...source the positive and negative of PC 00 PC 15 determine the running direction If it is negative it means the inverter runs in the opposite direction Figure 6 33 Simple PLC schematic 2 Always cycle...

Page 77: ...0 Section 7 Acc and dec time selection Section 8 Acc and dec time selection The 9th paragraph Acc and dec time selection Section 10 Acc and dec time selection Section 5 Acc and dec time selection PC 4...

Page 78: ...roup display selection Function parameter group display selection Function code modification attribute 0 Can be modified 1 not modifiable Default 0 Default 11 PP 04 Whether the user can set the functi...

Page 79: ...not need to be modified Only when there is a special requirement for the quality of the output voltage waveform or when the motor has an abnormality such as oscillation it is necessary to try to switc...

Page 80: ...ection point 1 input corresponding setting 100 0 100 0 Default 30 AI curve 4 inflection point 2 input A6 02 A6 06 Default 6 00V AI curve 4 inflection point 2 input corresponding setting 100 0 100 0 De...

Page 81: ...reset factory reset factory reset factory reset factory reset AC 01 AC 02 AC 03 AC 04 AC 05 AC 06 AC 07 AC 08 AC 09 AC 10 AC 11 factory reset factory reset factory reset factory reset This set of func...

Page 82: ...tips in this section to analyze the cause of the fault If the fault cannot be solved please seek technical support from our company or product agent Fault name Display Troubleshoot the cause Solution...

Page 83: ...stall the braking resistor 1 Instantaneous power failure occurs on the input power supply 2 The AC drive s input voltage is not within the allowable range 3 The bus voltage is abnormal 4 The rectifier...

Page 84: ...supply are faulty 2 The contactor is faulty 3 Three phase input power shortage 1 Replace the faulty driver board or power supply board 2 Replace the faulty contactor 3 check the three phase input powe...

Page 85: ...e control board or the operating panel is faulty 5 The cable connecting the control board and the driver board and the operating panel breaks 1 Check the power supply 2 Check the bus voltage 3 Re conn...

Page 86: ...E Inspection and maintenance of the inverter requires professional and qualified personnel and pay attention to the following matters Maintenance personnel must follow the specified methods of mainten...

Page 87: ...void storage in environments containing corrosive gases and liquids Long term storage will lead to deterioration of electrolytic capacitors It is best to ensure that the power is turned on within 2 ye...

Page 88: ...nication protocol defines the transmission information and use format in the series communication and it includes master polling or broadcasting format master coding method and the content includes fu...

Page 89: ...function code n CRC correction and H L Free Calculate CRC correction 1byte 2nbyte 2byte Master writes command frame 3 5byte 1byte 2byte Free Start frame Target station address Read the command 0x06 Fu...

Page 90: ...s extracted and examined If the LSB was a 1 the register is then exclusive Oared with a preset fixed value If the LSB was a 0 no exclusive OR takes place This process is repeated until eight shifts ha...

Page 91: ...l 4123 Present power on time 4107 AI1 voltage 4124 Present running time 4108 AI2 voltage 4125 Pulse input frequency unit 1Hz 4109 AI3 voltage 4126 Communication setting value 4110 Counting value input...

Page 92: ...fault during running 002A Too large speed deviation 002B Motor over speed 002D Motor overheat 005A Encode lines setting fault 005B Not connect to the encoder 005C Initial location fault 005E Speed fe...

Page 93: ...r power and resistance values for this drive According to the load the user can change the value appropriately but it cannot be less than the minimum required by the inverter During the running proces...

Page 94: ...00 598 620 390 300 11 350 745 780 480 360 12 Overall dimensions and mounting whole dimensions of the Keypad base and the Operating keyboard Chapter 9 FD300 3 050 C CE FD300 3 075 C CE FD300 3 100 C CE...

Reviews: