SPX100 SENSOR
DUST EMISSIONS CONTROLLER
Notice Technique
FI 72.0110.0316E
Page 18 sur 27
d) Enter the value of the current emissions level.
NOTE
: a message warns you if the value entered is "outside the limits". In this case, the
value of the scale entered previously may be poorly suited to your application.
There are two ways of removing this message:
- VALID button to enter a new value,
- RIGHT button to quit the auto-sensitivity procedure.
e) Enter the duration of a "test period" (1, 2, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55 ou 60
minutes).
Select a value which covers representative operation of the installation (unclogging,
arrival of unstable material etc).
f) The SPX 100 makes some tests to obtain an optimal sensor sensibility. The display
shows a message like that :
g) At the end of the test, 2 cases :
- The procedure finishes correctly, the device returns to measurement view with the new
settings.
- The procedure does not finish correctly, the display shows a warning message: "value
obtained <- - - > value to be obtained".
* VALID button to use the new setting.
* RIGHT button to quit and return to the initial settings.
NOTE
: - If the unit is switched off during an auto-sensitivity procedure, then the next
time it is switched on, a message states that the procedure was not correctly completed.