I) GENERALITIES
The SPX monitors and displays the dust emission behind a filter, based on the
triboelectric effect. It’s made with two main units self connected. It gives the trend of dust
emissions as a % or as a quantity (mg/m
3
or other).
- The sensor
: - installed in the duct or the duct to be monitored
- its extremity is projected into the particle flow
- monitored the signal
- The control unit
:
- receives the data from the sensor
- averaging measure
- converses with the user (display, keys)
- automatic zero calibration
- stores and dates the datas (1 month
of recordings)
- commands the alarm
- an output 4-20 mA (in option) of the trend
The SPX 100 can be connected with a PC (line RS232 and software in option) directly or
through a telephone MODEM
- remote viewing / configuration
- reading of the stored datas
- graph operation, reports creation, etc ...
- storage in disk files format
- graph display in continuous (real time)