SPX100 SENSOR
DUST EMISSIONS CONTROLLER
Notice Technique
FI 72.0110.0316E
Page 5 sur 27
II) CHARACTERISTICS
- Supply
115V or 230V
10%
- Frequency
50-60 Hz
- Power consumption
12 VA
- Relay contact parameters
Single pole changeover - 1A - 250V AC1
- Parameters adjustment
By keys on front panel with the user password
- Display
On alphanumerical LCD d backlight /
Leds bargraph
- Device protection
By fuse 500 mA
- Operating temperature
* part outside the duct:
0 à 65° C
* in the flow at the sensor:
< 85° C standard sensor
250° C sensor with thermal separator
> 250° C - please contact us
- Storage temperature
- 20 to 70° C
- Alarm threshold
Adjusting from 0 to full scale
(shown in alarm adjustment)
- Averaging measure
From 1 to 60 minutes
- Calendar
Retention 11 years (without supply)
Ac/- 1 minute per month maxi
Leap year / year 2000
- 1 month memory
Save by battery (kind : R6)
Retention 10 years (without supply)
- Display unit
µg/m
3
, mg/m
3
or % full scale
- Cable length sensor / base
10 meter in standard
(2)
- Sensor length
200 mm in standard
(2)
- 4-20 mA
(1)
Incorporated supply (
active) NOT INSULATED
Maxi load 500 ohms
- PC connection
(1)
RS232
(1)
: in option
(2)
: other on request