10-44
Serial Port Communications and Commands
Date Code 20020215
SEL-351R Instruction Manual
Use the BRE R command to reset the breaker/recloser contact wear monitor and trip operation
counters:
==>BRE R <ENTER>
RECLOSER R1 Date: 02/03/99 Time: 08:44:20.802
FEEDER 2101
Ctrl Trips= 16
IA= 40.7 IB= 41.4 IC= 53.8 kA
Ext Trips= 3
IA= 0.8 IB= 0.9 IC= 1.1 kA
Percent wear: A= 8 B= 7 C= 10
A-phase Trips= 14
B-phase Trips= 9
C-phase Trips= 10
EF/G Trips= 12
SEF Trips= 0
LAST RESET 12/27/98 15:32:59
Reset Trip Counters and Accumulated Currents/Wear
Are you sure (Y/N) ? Y <ENTER>
RECLOSER R1 Date: 02/03/99 Time: 08:44:33.920
FEEDER 2101
Cntrl Trips= 0
IA= 0.0 IB= 0.0 IC= 0.0 kA
Ext Trips= 0
IA= 0.0 IB= 0.0 IC= 0.0 kA
Percent wear: A= 0 B= 0 C= 0
A-phase Trips= 0
B-phase Trips= 0
C-phase Trips= 0
EF/G Trips= 0
SEF Trips= 0
LAST RESET 02/03/99 08:44:28
See
Breaker/Recloser Contact Wear Monitor
in
Section 8: Breaker/Recloser Monitor, Battery
System Monitor, Metering, and Load Profile Functions
for further details on the breaker
monitor.
CLO Command (Close Breaker)
The CLO (CLOSE) command asserts Relay Word bit CC for ¼ cycle when it is executed. You
can program Relay Word bit CC into the CL SEL
OGIC
control equation (see Figure 1.20) to
assert the CLOSE Relay Word bit, and, in turn, to assert an output (RCCL = CLOSE; see
Figure 7.30) contact to close a recloser.
See the
Close Logic
subsection in
Section 6: Close and Reclose Logic
for more information
concerning Relay Word bit CC and its recommended use.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......