Date Code 20020215
Breaker/Recloser Monitor, Battery System Monitor,
8-17
Metering, and Load Profile Functions
SEL-351R Instruction Manual
Keep 12 Vdc on While SEL-351R is “Asleep”
If both the following conditions are true when the SEL-351R puts itself to sleep, due to having
reached the
% Battery capacity for sleep
setting (e.g., 20% capacity):
•
Setting Keep the 12 V power on while asleep = Y
•
And the temperature-compensated battery voltage is above 80%
then the 12 Vdc power is kept on. This 12 Vdc power is available at the terminal block (see
Figure 9 in the
SEL-351R Quick-Start Installation and User’s Guide
). Use the 12 Vdc power
for such applications as keeping a radio on. If the temperature-compensated battery voltage falls
below 80%, the 12 Vdc power is shut off.
“Wake Up” the SEL-351R
When the SEL-351R is in the sleep mode, it wakes up when any of the following occur:
•
The 120 Vac source is reenergized
•
The front-panel WAKE UP pushbutton is operated
•
A “wake-up” message is received via the side panel Wake-up port
If the SEL-351R went to sleep because the temperature-compensated battery voltage fell below
80%, the Wake-up port is dead and cannot receive the wake-up message to wake up the
SEL-351R.
The wake-up message is a character string matching the
CHWAKE
global setting (SET G
command; default is CHWAKE = ABCD). When the SEL-351R receives this character string,
the SEL-351R wakes up and resumes its protection and control functions. The wake-up message
feature is intended to be used with remote communication via a radio connected to the Wake-up
port. The SEL-351R includes a 12 Vdc output to supply a radio—see preceding subsection
Keep
12 Vdc on While SEL-351R is “Asleep”
Introduction
subsection and Table 10.1 in
Section 10: Serial Port Communications and Commands
for more information on the Wake-up
port.
After the SEL-351R is awakened via the front-panel WAKE UP pushbutton, or the wake-up
message via the Wake-up port, the SEL-351R stays awake for 10 minutes after the last serial port
or front-panel port activity, unless the battery voltage falls below 70% of nominal, at which time
the SEL-351R puts itself to sleep again immediately, regardless of any other conditions.
Battery System Diagnostics
The SEL-351R monitors the 24 V battery system, including charge/discharge current, battery
voltage, and temperature. The SEL-351R calculates the capacity of the batteries based on these
measured values. The SEL-351R automatically applies a battery load test once per day and
includes provisions to manually perform a battery load test via the front-panel and serial
communication ports. You can obtain vital battery system information from the SEL-351R
status report via the front-panel and serial communication ports.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......