10-20
Serial Port Communications and Commands
Date Code 20020215
SEL-351R Instruction Manual
locator will attempt to run if the event report is generated by a trip (assertion of TRIP Relay
Word bit) or other programmable event report trigger condition (Access Level 2 SET L
SEL
OGIC
®
control equation setting ER). The fault locator should not be enabled unless three
phase voltage is connected to the control.
If the fault locator runs successfully, the location is listed in the LOCAT column, and the event
type is listed in the EVENT column:
AG
for A-phase to ground faults
BG
for B-phase to ground faults
CG
for C-phase to ground faults
AB
for A-B phase-to-phase faults
BC
for B-C phase-to-phase faults
CA
for C-A phase-to-phase faults
ABG
for A-B phase-to-phase to ground faults
BCG
for B-C phase-to-phase to ground faults
CAG
for C-A phase-to-phase to ground faults
ABC
for three-phase faults
If a trip occurs in the same event report, a “T” is appended to the event type (e.g., AG T).
If the fault locator does not run successfully, or if the fault locator is disabled (enable setting
EFLOC = N), $$$$$$$ is shown in the LOCAT column. In either case, the event type listed in
the EVENT column is one of the following:
TRIP
event report generated by assertion of Relay Word bit TRIP
ER
event report generated by assertion of SEL
OGIC
control equation event report
trigger condition setting ER
PULSE event report generated by execution of the PUL (Pulse) command
TRIG
event report generated by execution of the TRI (Trigger) command
The TARGETS column displays the front panel LED status during the event in binary format.
The top row of LEDs are shown first and the bottom row of LEDs are shown next under the
TARGETS column. A “1” means the LED was illuminated during the event and a “0” means the
LED was deasserted.
For example, 11001010 00001100 under the TARGETS column would be interpreted as follows
(first three digits):
1
à
Control Enabled LED illuminated
1
à
AC Supply LED illuminated
0
à
Battery Problem LED not illuminated
etc...
For more information on front-panel target LEDs, see
Front-Panel Status and Trip Target
LEDs
in
Section 1: Factory-Set Logic
. For more information on event reports, see
Section 12:
Standard Event Reports and SER
.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......