8-20
Breaker/Recloser Monitor, Battery System Monitor,
Date Code 20020215
Metering, and Load Profile Functions
SEL-351R Instruction Manual
Battery Status
You can check the battery status in several ways. On the front panel, the BATTERY PROBLEM
LED (see Figure 1.51) illuminates for any of the following battery problems:
•
Load test failure (Relay Word bit DTFAIL = logical 1)
•
Damaged, disconnected, or fuse is blown (battery cannot charge or discharge; Relay
Word bit NO BATT = logical 1)
•
Battery monitor/charger failure (Relay Word bit BCBOK = logical 0)
You also can press the STATUS pushbutton on the front panel of the SEL-351R to access more
battery status information. Use the secondary function up/down arrow pushbuttons to move to
different status screens. Those status elements of interest for the battery are the following:
MODE =
CHARGE –
battery is charged
≥
90% (trickle charging).
HICHRG
–
battery is charged < 90% (high charging).
DISCHRG
–
battery is discharging.
DISTST
–
battery load test in progress.
NOBATT
–
battery is damaged or disconnected (it cannot charge or
discharge).
FAIL
–
battery monitor/charger has failed or communications
with the battery monitor/charger are temporarily
interrupted.
%CAP =
0 to 100 –
battery charge level (independent of temperature).
HRS_LFT =
hh:mm—hours and minutes left to run on battery in discharge mode
before the SEL-351R puts itself to sleep (dependent on setting “%
Battery capacity for sleep [0-100]”). Shows XX:XX if battery is
charging.
5V_PSBC
internal 5 V power supply level for battery monitor/charger.
12V_AUX
voltage level of 12 V auxiliary output—available via terminal block
positions 23 and 24—controlled by two 12 V settings in the EZ Level
Global Settings.
VBAT =
voltage level of 24 V battery.
IBAT =
current level (in mA) at which the 24 V battery is charging or
discharging (preceded by a minus sign for discharging).
You can obtain the same battery status information as described above via serial port
communication using the STATUS command.
Additional Application
In addition to alarming, you can use the relay elements associated with the battery and charging
system to perform control functions, such as to disable or block reclosing. For example, the
factory default logic settings include the following automatic reclose supervision setting:
79CLS = 59A1 * BCBOK * !NOBATT * !DTFAIL
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......