9-26
Setting the SEL-351R Recloser Control
Date Code 20020215
SEL-351R Instruction Manual
Row
Bit
Definition
Primary
Application
67Q1T**
Level 1 negative-sequence definite-time overcurrent
element 67Q1T timed out (derived from 67Q1; see
Figure 3.12)
67Q2T**
Level 2 negative-sequence definite-time overcurrent
element 67Q2T timed out (derived from 67Q2; see
Figure 3.12)
67Q3T**
Level 3 negative-sequence definite-time overcurrent
element 67Q3T timed out (derived from 67Q3; see
Figure 3.12)
67Q4T**
Level 4 negative-sequence definite-time overcurrent
element 67Q4T timed out (derived from 67Q4; see
Figure 3.12)
14
50P5
Level 5 phase instantaneous overcurrent element
(maximum phase current above pickup setting
50P5P; see Figure 3.2)
Tripping,
Control
50P6
Level 6 phase instantaneous overcurrent element
(maximum phase current above pickup setting
50P6P; see Figure 3.2)
50N5
Level 5 neutral ground instantaneous overcurrent
element (neutral ground current [channel IN] above
pickup setting 50N5P; see Figure 3.9)
50N6
Level 6 neutral ground instantaneous overcurrent
element (neutral ground current [channel IN] above
pickup setting 50N6P; see Figure 3.9)
50G5
Level 5 residual ground instantaneous overcurrent
element (residual ground current above pickup
setting 50G5P; see Figure 3.11)
50G6
Level 6 residual ground instantaneous overcurrent
element (residual ground current above pickup
setting 50G6P; see Figure 3.11)
50Q5**
Level 5 negative-sequence instantaneous overcurrent
element (negative-sequence current above pickup
setting 50Q5P; see Figure 3.13)
Control
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......