D-12
Configuration, Fast Meter, and Fast Operate Commands
Date Code 20020215
SEL-351R Instruction Manual
BNA Message
In response to the BNA command, the relay sends names of the bits transmitted in the Status
Byte in the A5D1 message. The first name is the MSB, the last name is the LSB. The BNA
message is:
<STX>"*","*","*","STSET","*","*","*","*","yyyy"<ETX>
where:
"yyyy" is the 4-byte ASCII representation of the checksum.
"*" indicates an unused bit location.
The BNA command is available from Access Level 1 and higher.