Date Code 20020215
Distributed Network Protocol (DNP) V3.00
H-11
SEL-351R Instruction Manual
D
ATA
M
AP
The following is the default object map supported by the SEL-351R (FID = SEL-351R-Rxxx-
V0-Zxxxxxx-Dxxxxxxxx).
Table H.3: SEL-351R DNP Data Map
DNP Object Type
Index
Description
01,02
000–499
Relay Word, where 50B3 is 0 and 50NF is 447 (LT9 is
471 for the SEL-351R-2.)
01,02
500–999
Relay Word from the SER, encoded same as inputs
000–499 with 500 added.
01,02
1000–1015
Relay front-panel targets, where 1015 is RESET, 1008 is
SEF, 1007 is CONTROL ENABLED, and 1000 is 81.
01,02
1016–1019
Power factor leading for A-, B-, C-, and 3-phase.
01,02
1020
Relay Disabled.
01,02
1021
Relay diagnostic failure.
01,02
1022
Relay diagnostic warning.
01,02
1023
New relay event available.
01,02
1024
Settings change or relay restart.
01,02
1
1025
A more recent unread relay event is available.
(These 10,12 Object Types apply to the SEL-351R-0, -1 only.)
10,12
00–07
Remote bits RB1–RB8.
10,12
08
Pulse Open command OC.
10,12
09
Pulse Close command CC.
10,12
10
Reset demands.
10,12
11
Reset demand peaks.
10,12
12
Reset energies.
10,12
13
Reset breaker monitor.
10,12
14
Reset front-panel targets.
10,12
15
Read next relay event.
10,12
16–19
Remote bit pairs RB1–RB8.
10,12
20
Open/Close pair OC & CC.
(These 10,12 Object Types apply to the SEL-351R-2 only.)
10,12
00–15
Remote bits RB1–RB16.
10,12
16
Pulse Open command OC.
10,12
17
Pulse Close command CC.
10,12
18
Reset demands.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......