25
2021-02-10 / V1.0
Contactors C195 Series – Installation and Maintenance Instructions
Installation
7.2.6 Connecting the coil
ATTENTION
The value of the overvoltage limitation is part of the
magnetic system and must not be modified and in
particular not be short-circuited (e.g. by an external
diode).
X
Make sure that no such diode is used in your
control circuit.
ATTENTION
X
Bending of the coil terminals is not permitted!
X
Move and route the control wires and recep-
tacles only in the direction of plugging, see
Fig. 23
to
Fig. 28
.
X
Mechanically secure the control wires to mini-
mise feedback effects of forces caused by the
wires (e. g. shock, vibrations) acting on the ter-
minals.
The control wires for the coil terminals must be fitted
with flat receptacles (6.3 x 0.8 mm).
X
Plug the pre-assembled control wires with the re-
ceptacles (4) to the both coil terminals A1 and A2.
X
If applicable bundle and secure the wires using
cable ties.
6.3 x 0.8 mm
5
4
Fig. 23: C195 X/: Connecting the coil
6.3 x 0.8 mm
5
4
Fig. 24: C195 A/, C195 B/: Connecting the coil (the figure
shows C195 A, the procedure is identical for C195 B/)
6.3 x 0.8 mm
5
4
Fig. 25: C195 S/, C195 T/: Connecting the coil (the figure shows
C195 S/, the procedure is identical for C195 T/)