54
2021-02-10 / V1.0
Maintenance
Contactors C195 Series – Installation and Maintenance Instructions
8.4.3 Replacing the complete contact
unit – type C195 A/, B/, S/, T/, W/
Spare parts required
-
Contact unit complete, see chapter
“9. Spare parts”
Tools required
-
Set of Torx bits or Torx screwdriver set
-
Continuity tester
-
Torque spanner
Disassembly
DANGER
Before beginning any work on the con-
tactors, make sure that
X
there is no voltage present,
X
all safety regulations are fully ob-
served.
X
Be sure to observe section
“8.1 Safety” on page 32
.
X
Remove all connecting cables or busbars from the
main contacts, auxiliary switches and coil connec-
tions.
ATTENTION
Incorrect installation of the contact unit due to two
possible installation positions leads to malfunctions
and destruction of the contactor.
X
Before disassembling, note the orientation of
the old contact unit in relation to the base plate.
X
Disassemble the contact unit, see section
“Dis-
assembling/assembling the contact unit –
type C195 A/, B/, S/, T/, W/” on page 46.
Assembly
ATTENTION
Incorrect installation of the contact unit due to two
possible installation positions leads to malfunctions
and destruction of the contactor.
X
Before installing the contact unit on the mag-
netic drive, observe the previously noted cor-
rect orientation in relation to the base plate.
X
Screw the new contact unit to the magnetic drive
using the two new screws supplied and tighten
them to a torque of 0.8-1 Nm.
See section
„Disassembling/assembling the con-
tact unit – type C195 A/, B/, S/, T/, W/“ on page
46.
X
Reconnect all connecting cables or busbars (main
contacts, auxiliary switches and coil connections),
see
“7.2 Electrical connection” on page 21.
X
Finally, subject the contactor to a complete check
as described in section
“7.4 Checks” on page 31
.