Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Registers, configuration
Register usage
5-2
5
Registers
Description
112*
Configuration of the watchdog
0
The watchdog stops the controller
(closes all valves and stops the fan)
1
The watchdog executes a restart of the controller
(closes all valves and stops the fan)
General
74
Controller type:
1
PCD7.L60x
2
PCD7.L79xN
75
Software version (read only):
E.g. 108 means Version 1.08
126
32-bit register for storing any type of information. This is a free register available
to the user for 'Read' and 'Write' use. As the information is permanently stored
in EEPROM, it cannot be written to cyclically. The content has no effect on the
control program. It is possible to store a version number or the last commissioning
date in it.
Room control unit
104
Manual set-point adjustment on the room control unit in up to +/- 6 steps.
[K/10 and step]
Range: 0
…
10 (=0
…
1.0 K/step), Default: 5
Function
9
Application selection. Default:5
The valve outputs for heating/cooling are defined via register 103 under the
heading "Hardware". TRIAC-PWM , TRIAC-3-point and 0
…
10 V are available.
All outputs not used by the application can be controlled via the communication
function (RIO operation).
0
RIO operation; all outputs can be controlled via the Bus.
1
2-tube heating, heating valve: Y1(Y3)
2
2-tube change-over, valve: Y1(Y3)
Register 38 defines the control mode 'Heating' or 'Cooling'. Depending on the
hardware setting, it is controlled by contact input E2 or the S-Bus.
3
2-tube cooling. Cooling valve: Y1(Y3)
5
4-tube heating/cooling.
Heating valve: Y1(Y3) Cooling valve: Y2(Y4)
7
2-tube heating with 2 valve outputs controlled in parallel
Heating valve 1: Y1(Y3) Heating valve 2: Y2(Y4)
8
2-tube change-over with 2 valve outputs controlled in parallel
Valve 1: Y1(Y3) Valve 2: Y2(Y4)
9
2-tube cooling with 2 valve outputs controlled in parallel
Cooling valve 1: Y1(Y3) Cooling valve 2: Y2(Y4)