Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Functions, manual output control
Function
3-25
3
FBox outputs "L79x Room"
“-Occupied, presence”
Parameter for detection of presence.
“-SetPt”, control set point
Actual control set point taking account of any manual interventions and limitations.
“-Temp”, actual value
Actual value as input signal to the two PI controllers for heating and cooling. The
measurement point can be defined via the configuration. (See "Function, settings,
hardware").
“-HeatY”, heating valve
Control of heating valve in in [%].
“-CoolY”, cooling valve
Control of cooling valve in in [%].
“-Err”, error flag
FBox internal output for detecting communication errors. If a transmission with all
telegram repeats fails completely, the FBox disables communication until the next
attempt by the Setup FBox. The retry time is defined in seconds in the Setup FBox
via the internal parameter "Pause after communication error".
A description of the L79x Room FBox settings can be found in the online help for
Saia PG5
®
.