Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Functions, settings
Function
3-14
3
3.2.4 Functions, settings, control parameters
Heating:
Set-point
Cooling
Y
Comfort
Standby
Frost protection
XW
Reduced
Base set-point (register 37)
After a restart, the active control set-point (register 41) is initialised with the base set-
point value.
Range of settings: (default 22 °C)
FBox
10 … 35 °C
Registers
100 … 350 °C/10
Deadband comfort mode °K (register 2)
Range of settings: (default 2 K)
FBox
0 … 20 K
Registers
0 … 200 K/10