Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Application overview
Overview
1-6
1
1.3.1 Device overview and technical details of the compact room controller
Type: PCD7. ...
L790
N
L791N
L792N
L793N
Functions
One output sequence
×
Two output sequences
×
×
×
TRIAC output
×
×
×
×
0…10 V output
×
Changeover function
×
×
×
×
Presence key
×
×
Set-point setting
×
×
LED display
×
×
S-Bus slave operation
×
×
×
×
NTC Internal temperature
sensor
×
×
×
×
Additional inputs:
Digital inputs:
presence
/
window
2
2
2
2
Analogue inputs 0…10 VDC:
1
General details
Temperature sensor, internal:
NTC 10
kΩ
/
0…40 °C
Control behavior:
P or PI behavior
Communication interface:
SBC S-Bus
/
RS-485 interface
/
Data mode
/
4
800, 9
600, 19 200, 38 400, 115 200 bit/s with
automatic detection at restart time.
Power consumption:
1.5 W without actuating drives
TRIAC output specification:
24
VAC
/800 mA max.
TRIAC mode:
Direction invertible
Output spec. 0…10 VDC: 0…10 VDC
/
max. load 2 mA
Housing:
Plastic, white, surface mounted, IP20 protection
Dimensions: 82
× 117 × 31 mm (W × H × D)