Saia-Burgess Controls AG
Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Application overview
Overview
1-7
1
Maximum number of room controllers
The maximum number of room controllers that can be processed by a PCS
/
PCD
system is dependent on the Bus cycle time and the resources used by the function
objects.
Resources:
max. 600 lines of code per FBox ,
max. 30 registers per FBox,
max. 10 flags per FBox, 1 DB
Bus cycle time per controller: approx. 15 ms
PCD program cycles:
428 for 150 FBoxes, measured with PCD3.M5540
Commissioning
When the room controller is used in a SBC
S-Bus network, configuration is either by
the Saia Burgess Controls PCS/PCD Master or the Saia PG5
®
programming tool.
Practical function blocks (FBoxes) simplify commissioning.
FBox library
Saia PG5
®
FUPLA FBox-Selector
The "Room Control PCD7.L79xN" FBox library for the single room controller contains
all the FBoxes needed for Saia PG5
®
. It can be dlwonloaded free of charge from the
Saia Burgess Controls home page at:
www.sbc-support.com