Procedure for the temperature calibration on commissioning
Commissioning instructions
2-5
2
Carry out only if necessary:
2) Dynamic calibration (Register 29)
This setting depends on the connected thermal valves type and quantity and on the
installation-conditions. This calibration is not mandatory and can be performed at spe-
cific room constellation in which the measurement accuracy is not sufficient.
a) Connect the thermal valves and activate (over the setpoint)
the PWM outputs to 100 %.
b) After 30 minutes the temperature has to be measured near to the lower air slots
and to compare with the measured temperature of the controller.
c) When the displayed temperature of the controller is too high, then it is possible
to set a higher stage for the “dynamic correction” (stage 1 up to 5).
Stage Effect
None Without dynamic correction
1
increase of the dynamic correction
2
3
4
5
Maximum → for several parallel connected valves