Manual for PCD7.L79xN room controllers
│
Document 27 / 602
E
N02 │ 2013-11-27
Communication
Function
3-3
3
- C
o
nnect
S
bus 252.
-
W
rite
R
egister 110 - new station number.
-
W
rite
R
egister 60 - 0.
Automatic configuration
The compact room controllers can be configured automatically via the Config and
Room FBoxes. After every restart, a flag is passed to the Room FBox to tell it that the
controller has been restarted. The FBox then checks that the configuration matches
the associated Config FBox. If this is not the case, all the control parameters are
copied over automatically from the Config FBox to the compact room controller. This
option reduces commissioning to the address-setting operation. This means that
after a device replacement in the course of support work, functionality can be reliably
restored by the Saia PCD
®
alone.
See also the description of the individual functions in the following sections.