6
6.1.2 Electrical load on Serial S-Net
The compact room controller have a high impedance and place only a small load on
Serial S-Net. They have an 8× higher impedance than a Standard-Receiver.
Limited by the electrical load on the Serial S-Net system, a segment (without
repeater) can have no more than 32 Saia PCD
®
controls or 248 compact room
controllers connected to it.
Limited by the Bus cycle time, a maximum of 127 compact room controllers can be
used in one segment (without repeater).
Number of Saia PCD
®
systems on a Serial S-Net line:
Number of Saia PCD
®
controls
Number of compact room controllers
1
127
2
126
…
…
18
110
19
104
20
96
21
88
…
…
31
8
32
0