29
00-04
Machine ON Display Selection
Factory setting
0
Setting range
0:Displaying setting frequency (F)
1:Displays current running frequency (H)
2:Display multi-function contents(00-05)( U)
3:Displays running current (A)
4:FWD/REV RUN reference
This parameter can be set the default display ,"2" optional contents is set and displayed according to 00-05.
00-05
Determining multifunctional display
Factory setting
0
Setting range
0:
Displaying output voltage
1:
Displaying DC-BUS voltage
2:
Displaying count value
3:
Displaying rotating speed
This parameter is displaying content , when the boot screen selection is 00-04 parameter, and this parameter is
set to 02.
1 Basic Parameters
01-00
Master Frequency Input Setting(simulation feedback
input estimated frequency)
Factory setting
0
Setting range
0:The master frequency input is controlled by digital exerciser
1:Reserved
2:Master frequency is input by analog signals AVI1(DC0 to +10V)
3:Master frequency is input by analog signals ACI (DC 4 to 20mA) /(DC 0 to +5V)
4:Master frequency is controlled by RS485 communication interface
5:Master frequency is controlled by external UP/DOWN pin
6:Reserved
This parameter is used to set the AC drive main frequency source. However, the actual AC drive running
frequency would be control by [Jogging frequency], [Multi-step speed 1-7] or [Up / Down frequency], using the
Multi-function inputs 1, 2, and 3. Refer to 02-01,02,03.
01-01
Operation Command Source Setting
Factory setting
0
Setting range
0:Operated by digital exerciser
1:Operated by external terminals. STOP on keyboard available
2:Operated by the control keyboard of the external terminals. STOP on keyboard
unavailable
3:Operated by Communication Interface RS485. STOP on keyboard available
4:Operated by Communication Interface RS485. STOP on keyboard unavailable
This parameter is used to set the source of the AC Drive operating instructions.