02:External Terminal Parameters
Set during running available * the values of different machine models are different.
Parame
ter
Parameter functions
Setting range
Factory
setting
02-04
External terminal frequency UP/DN
key constant speed rate
0.01
~
1.00 Hz/ms
0.01
02-05
Digital input response time
2
~
2000 ms
20
02-06 Appointed count setting
1
~
9999
1
02-07 Count value agreement setting
1
~
9999
1
02-08
Multiplier setting for digital output
frequency
1
~
20
1
02-09
Multifunctional output terminal
1(MO1)
0:Reference during running
1:Set frequency agreement reference
2:Random frequency agreement reference
3:Count agreement reference
4:non-zero speed
5:Over-torque detection reference
6:reserved
7:Low voltage detection reference
8:Operation mode of AC motor drive
9:Fault reference
0
02-10
Multifunctional output terminal
2(MO2)( reserved)
1
02-11
Random frequency agreement
setting
0.00
~
600.00 Hz
0
02-12
Multifunctional output contactor
indication
Normally Open Contactor(RA-RC)
Normally Closed Contactor(RB-RC)
0:Fault reference
1:Reference during running
2:Set frequency agreement reference
3:Random frequency agreement reference
4:non-zero speed
5:Over-torque detection reference
6:reserved
7:Low voltage detection reference(LU)
7
02-13 Analog output signal setting
0:Analog frequency meter(0 to max
operation frequency)
1:Analog current meter(0 to 200% of rated
current)
0
02-14
Analog output gain setting
1
~
200%
100
03:Analog output / input function parameters
Set during running available * the values of different machine models are different.
Parame
ter
Parameter functions
Setting range
Factory
setting
03-00
Upper frequency analogue voltage
setting
0.0
~
10.0 V
9.5
03-01
Lower frequency analogue voltage
setting
0.0
~
10.0 V
0.3
03-02 Analogue input filter time
0.01
~
2.00 Sec
0.05
03-03 Given gain for analog
0
~
200%
100